Central Control Of Room Operating Mode Via Input From The Use Schedule - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

K N X
CO
R
Note
Effective room operating
mode
Switching state
Building in use
Building not in use
Protection
Siemens
Building Technologies
The state of the room controller (result of the logic OR operation) is mapped to the
building automation and control system via the following S-mode communication object:
Window contact output (Output communication object)
Flags
Type
R W C T U
1 0 1 1 0 1.019
DPT_WindowDoor
Master/slave applications:
Bindings are required in S-mode to communicate to the master the window contact
state at the slave.
5.3.2
Central control of room operating mode via input from
the Use schedule
Central
Local
Controller
Prio
S
1.
DI
2.
S
3.
S
S
DI
3.
PPS2
3.
S
The table below shows the three possible occupancy states and the resulting Effective
room operating mode.
Description
• Full availability of all plants.
• Building enabled for use.
• Priority 3 influences are enabled (schedule
occupancy, presence detector, room unit, and
Temporary Comfort mode).
• Reduced availability of the plants.
• Priority 3 influences are disabled (schedule
occupancy, presence detector, room unit, and
Temporary Comfort mode).
• Application:
For temporary vacancy.
The building must reach the Comfort
temperature within hours.
• Setpoints are at levels required to protect the
building.
• Priority 3 influences are disabled (schedule
occupancy, presence detector, room unit, and
Temporary Comfort mode).
• Application: Extended building vacancy.
RXB (KNX) Applications library
Room operating modes
Send heartbeat
Yes
This schedule determines the overall period of time
for which the entire building is in use. Typically, it is
used for night setback throughout the building or for
S
long periods when the building is not in use.
When the building is not used, interventions of third
priority are disabled. This prevents demand signals
S
from being sent to the primary plant when e.g. a
security guard enters a room.
CLC and RAD description of functions for CC-02 CM110384en_03
States
0 = Closed
1 = Open
Effective room operating
mode
According to schedule
occupancy , presence
detector, or room unit
Economy
Protection
35/140