Note
70/166
Siemens
Building Technologies
6.1.1
Bus output for current setpoints
The present setpoints can be integrated in the building automation and control system
via the following S-mode communication objects individually or as triplets :
Present Eco cooling setp (Output communication object)
Present Precomf cooling setp (Output communication object)
Present Comf cooling setp (Output communication object)
Present Comf heating setp (Output communication object)
Present Precomf heat setp (Output communication object)
Present Eco heating setp(Output communication object)
Flags
Type
R W C T U
1 0 1 1 0 9.001
DPT_Value_Temp
Present setpoints heating (Output communication object)
Present setpoints cooling (Output communication object)
Flags
Type
R W C T U
1 0 1 1 0 222.100
DPT_TempRoomSetpSetF16[3]
6.1.2
Bus output effective setpoints
For integration into a building automation and control system, the controller maps the
effective setpoints associated with the effective room operating mode to the following
communication object:
Effective setpoint (Output communication object)
Effective setpoint heating (Output communication object)
Effective setpoint cooling (Output communication object)
Flags
Type
R W C T U
1 0 1 1 0 9.001
DPT_Value_Temp
If the room temperature is in the dead band, the Effective setpoint transmitted by the
controller is either the heating or the cooling setpoint, depending on the controller's last
activity.
6.1.3
Bus outputs LTE mode
In LTE-mode, the current and effective setpoints are not transmitted to the building
automation and control system.
RXB (KNX) application library
Setpoint calculation
Send
heartbeat
yes
Send
heartbeat
yes
Send heartbeat
yes
FNC Description of functions for FC-10, FC-11, FC-12
Values
Floating point (°C)
Values
3 floating point values
- Comfort (°C)
- Precomfort (°C)
- Economy (°C)
Value
Floating point (°C)
CM110385en_05
28 Feb 2009