Two-pipe fan coil with changeover
Plant diagram
N1
Room controller.
R1
Room unit with temp.
sensor.
B1
Return air sensor.
D1
Window switch.
D2
Presence detector.
D3
Changeover signal via KNX
bus.
Q1
Fan (1 ... 3 speeds).
YHC Heating/cooling valve.
Operating diagrams
Y
Output signal.
TR
Room temperature.
SpH
Effective heating setpoint.
SpC
Effective cooling setpoint.
H
Heating sequence.
C
Cooling sequence.
YHC
Heating/cooling valve.
Q14
Fan speed 1.
Q24
Fan speed 2.
Q34
Fan speed 3.
Siemens
Building Technologies
Heating only (with LTHW), cooling only (with CHW) or changeover.
Changeover via KNX bus.
Modulating control of heating/cooling valve.
Automatic or manual fan control.
D3
YHC
N1
K N X
R
Y [%]
Change-over
H
100
YHC
YHC
0
SpH
SpC
Change-over
Y
H
Q34
Q24
Q14
SpH
SpC
RXB application library (KNX)
FNC02 – Two-pipe fan coil with changeover
Q1
T
B1
T
R1
D1
10385D45
C
TR [°C]
10385D34
C
TR [°C]
FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12
FNC02
K NX
D2
CM110672en_03
30.11.2007
R
3/52