Four-pipe fan coil
Plant diagram
N1
Room controller.
R1
Room unit with temp.
sensor.
B1
Return air sensor.
D1
Window switch.
D2
Presence detector.
Q1
Fan (1... 3-speed).
YH
Heating valve.
YC
Cooling valve.
Operating diagrams
Y
Output signal.
TR
Room temperature.
SpH
Effective heating setpoint.
SpC
Effective cooling setpoint.
H
Heating sequence.
C
Cooling sequence.
YH
Heating valve.
YC
Cooling valve.
Q14
Fan speed 1.
Q24
Fan speed 2.
Q34
Fan speed 3.
Siemens
Building Technologies
•
Heating with LTHW and cooling with CHW.
•
Modulating control of heating and cooling valve.
•
Automatic or manual fan control.
YC
YH
N1
K N X
R
Y [%]
H
100
YH
0
SpH
SpC
Y
H
Q34
Q24
Q14
SpH
SpC
RXB application library (KNX)
FNC04 – Four-pipe fan coil
Q1
T
B1
T
R1
C
YC
TR [°C]
C
TR [°C]
FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12
FNC04
K NX
D1
D2
CM110672en_03
R
15/52