K N X
CO
R
100/166
Siemens
Building Technologies
The power consumption is mapped to the following communication object:
Electric output (Output communication object)
Flags
Type
R W K T U
1 0 1 1 0 9.024
DPT_Power
8.5

Fan-coils with LTHW radiator (FNC18)

LTHW radiator applications have a proportional control sequence. The controllers
operate with a PI algorithm optimized for thermal or motorized valve actuators. (For
simplicity, the diagram below shows only the P-control action.)
The radiator sequence can also be used for other heating types, e.g. floor heating.
However, the control parameters are not optimized for this.
The heater battery of the fan-coil operates in a cascade with the radiator.
The control sequences come into operation at the effective heating setpoint.
B1
T
D3
YHC
T
YH
Y [%]
Y [%]
Change-over
Change-over
H
H
100
100
YH
YHC
0
0
SpH
SpH
8.5.1

Configuration and parameter setting

The radiator as an additional heating sequence has its own settings for the valve
actuator and runtime. The principles are described in section 8.1.4 .
RXB (KNX) application library
Control sequences
Send heartbeat
yes
Q1
B1
T
Y
Output signal
C
C
TR
Room temperature
SpH
Effective heating setpoint
H
Heating sequence
YHC
YH
Heating valve (radiator)
YHC
Heating/cooling valve (fan coil)
B1
Return air sensor
Q1
Fan
TR [°C]
TR [°C]
SpC
SpC
FNC Description of functions for FC-10, FC-11, FC-12
Value
Floating point (kW)
CM110385en_05