General Data - 8½, , , , , 10 Ton High Efficiency - Trane Voyager Manual

Product
Table of Contents

Advertisement

Table 18-1
General Data
Cooling Performance
1
Gross Cooling Capacity
EER
2
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
3
Integrated Part Load Value
System Power (KW)
Heating Performance
4
Heating Models
Heating Input (Btuh)
1st Stage
Heating Output (Btuh)
1st Stage
5
AFUE%
Steady State Efficiency (%)
5
No. Burners
No. Stages
Gas Connection Pipe Size (in.)
Compressor
No./Type
Sound Rating (BELS)
6
Outdoor Coil - Type
Tube Size (in.) OD
Face Area (sq ft)
Rows/FPI
Indoor Coil - Type
Tube Size (in.)
Face Area (sq ft)
Rows/FPI
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan - Type
No. Used/Diameter (in.)
Drive Type/No. Speeds
CFM
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter (in.)
Drive Type/No. Speeds
No. Motors
Motor HP (Standard/Oversized)
Motor RPM (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
Filters - Type
Furnished?
(No.) Size Recommended
7
Refrigerant Charge (Lbs of R-22)
/Circuit
NOTES:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and
includes the effect of fan motor heat. Rated in accordance with ARI Standard 210/240 or 360
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based On ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
5. AFUE and Steady State Efficiency is rated in accordance with DOE test procedures.
6. Sound Rating is rated in accordance with ARI Standard 270 or 370.
7. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
8. Face Area for Indoor Coil on Horizontal models is 12.36.
9. Horizontal Models have 4 -20 x 25 x 2 filters.
10. The refrigerant charge for Horizontal models is 7.8/8.1.
Indicates both downflow and horizontal units.
General
Data
8½ Ton Downflow and Horizontal Units
YC 103C3,C4,CW
106,000
11.00
3,400 / 3,000
101,000
11.9
9.18
Low
High
150,000
250,000
100,000
175,000
122,000
203,000
81,000
142,000
81.0
81.0
81.0
81.0
1
1
2
2
1/2
1/2
2/Copeland Scroll
9.0
Hi-Performance
0.375
23.93
2/16
Hi-Performance
0.375
12.63
8
3/15
Short Orifice
1/1.0 NPT
Propeller
1/26
Direct/1
7,100
1/1.0
1125
FC Centrifugal
1/15 x 11
Belt/1
1
2.0/3.0
1740/1740
145T/145T
Throwaway
Yes
(3)20 X 20 X 2/(3)16 X 20 X 2
9
10
9.1/9.5
18
8½, , , , , 10 Ton
High Efficiency
10 Ton Downflow and Horizontal Units
YC 121C3,C4,CW
127,000
11.50
4,000 / 3,500
120,000
12.4
10.43
Low
High
150,000
250,000
100,000
175,000
122,000
203,000
81,000
142,000
81.0
81.0
81.0
81.0
1
1
2
2
1/2
1/2
2/Climatuff®
9.2
Hi-Performance
0.375
28.21
2/16
Hi-Performance
0.375
17.50
3/15
Short Orifice
1/1.0 NPT
Propeller
2/26
Direct/1
10,800
2/0.5
1100
FC Centrifugal
1/15 x 15
Belt/1
1
2.0/3.0
1740/1740
145T/145T
Throwaway
Yes
(2)20 X 20 X 2/(4)20 X 25 X 2
11.0/11.0