Table 39-1
Evaporator Fan Performance 6¼ And 7½ Ton YC 075C, YC 090C
Unit
.10
Tons
Model No.
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1 HP Standard Motor & Field
Supplied Low Static Drive
2000 659 .46 715 .53 771 .60 822 .67 873
2250 728 .63 778 .71 828 .79 877 .87 922
YCH075C-H
2500 798 .84 843 .93 888 1.02 934 1.11 977 1.20 1018 1.28 1058 1.37 1099 1.46 1140 1.55 1181 1.64
2750 869 1.10 910 1.20 951 1.29 993 1.39 1033 1.49 1073 1.58 1110 1.68 1147 1.78 1183 1.87 1221 1.97
3000 940 1.41 979 1.51 1016 1.62 1054 1.72 1092 1.83 1129 1.94 1165 2.04 1200 2.15 1234 2.25 1267 2.36
1 HP Standard Motor & Field
Supplied Low Static Drive
2000 597 .39 646 .44 692 .50 739 .55 782
YCD075C-L,H
2250 659 .53 705 .59 745 .65 787 .72 829
YCH075C-L
2500 723 .71 765 .78 802 .85 839 .92 877
2750 789 .93 826 1.01 862 1.08 895 1.15 928 1.23 963 1.31 997 1.38 1030 1.45 1061 1.53 1092 1.60 1171 1.79 1244 1.97
3000 855 1.19 887 1.27 922 1.36 953 1.44 983 1.52 1014 1.60 1046 1.68 1078 1.76 1108 1.85 1137 1.93 1209 2.13
2 HP Standard Motor & Field
Supplied Low Static Drive
2400 795 .75 845 .81 891 .87 938 .94 983
2700 884 1.05 926 1.12 970 1.19 1010 1.26 1052 1.33 1093 1.39 1131 1.44 1167 1.49 1203 1.54 1241 1.59
YCH090C-H
3000 974 1.42 1010 1.50 1051 1.58 1089 1.65 1125 1.73 1162 1.80 1200 1.88 1235 1.94 1268 1.99
3300 1064 1.87 1097 1.95 1133 2.04 1170 2.13 1203 2.21 1235 2.29 1270 2.38
3600 1154 2.41 1185 2.50
2400 721 .62 760 .66 801 .71 840 .76 879
YCD090C-L,H
2700 802 .86 836 .92 872 .97 908 1.03 943 1.08 977 1.13 1011 1.17 1043 1.22 1075 1.27 1108 1.31 1186 1.40 1259 1.47
YCH090C-L
3000 884 1.17 915 1.23 946 1.29 979 1.35 1011 1.41 1042 1.47 1073 1.52 1104 1.57 1134 1.63 1163 1.68 1236 1.80
3300 966 1.54 994 1.60 1022 1.67 1051 1.73 1081 1.80 1111 1.87 1139 1.93 1167 1.99 1195 2.05 1223 2.11
3600 1048 1.98 1075 2.06 1101 2.12 1126 2.20 1153 2.27 1181 2.34 1208 2.42 1234 2.49 1260 2.55
Table 39-2
Evaporator Fan Performance 7½ Ton Dual Compressor YC 090D
Unit
.10
Tons
Model No.
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Field Supplied
Low Static Drive
2400 769 0.72 817 0.78 864 0.84 911 0.90 957 0.96 1000 1.01 1041 1.05 1082 1.10 1125 1.14 1169 1.18
2700 854 1.00 897 1.07 939 1.14 980 1.21 1022 1.28 1064 1.34 1103 1.40 1140 1.45 1177 1.50 1213 1.55
YCH090D-H
3000 940 1.35 978 1.43 1016 1.51 1054 1.58 1092 1.66 1129 1.74 1167 1.81 1204 1.88 1238 1.94 1271 2.00
3300 1027 1.77 1062 1.86 1096 1.95 1131 2.04 1165 2.12 1199 2.20 1233 2.29 1268 2.37
3600 1115 2.28 1146 2.38 1178 2.48
2400 698 0.59 739 0.64 779 0.69 819 0.74 857 0.78 895 0.82 931 0.86 967 0.90 1004 0.94 1039 0.97 1121 1.04 1203 1.09
YCD090D-L,H
2700 775 0.82 813 0.88 848 0.93 884 0.99 919 1.04 953 1.09 987 1.14 1020 1.19 1052 1.23 1084 1.28 1164 1.38 1237 1.45
YCH090D-L
3000 853 1.11 888 1.18 920 1.24 952 1.30 984 1.36 1016 1.42 1047 1.47 1077 1.53 1108 1.58 1137 1.63 1209 1.76
3300 932 1.46 963 1.53 994 1.60 1023 1.67 1052 1.74 1081 1.80 1110 1.87 1138 1.93 1166 1.99 1194 2.05 1261 2.20
3600 1011 1.88 1040 1.96 1069 2.04 1096 2.11 1122 2.18 1148 2.26 1176 2.33 1203 2.40 1229 2.47 1254 2.54
Data includes pressure drop due to filters and wet coil.
Fan motor heat (MBH) = 3.53 x Fan Bhp.
Trane's factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
NOTES:
1. Field supplied Browning fan sheave AL74 and Belt A48 required.
2. Field supplied Browning motor sheave IVL34 and Belt A48 required.
Performance
Data
External Static Pressure (Inches of Water)
.20
.30
.40
.50
1
1 HP Standard Motor & Sheaves
.74 924 .81 975 .88 1026 .96 1078 1.04
.95 967 1.03 1013 1.11 1058 1.19 1103 1.27 1148 1.35
2 HP Oversized Motor & Sheaves
1
.60 825 .66 868 .71 907 .76 947 .81 986 .86 1082 .98
.78 867 .84 905 .90 944 .96 982 1.02 1017 1.08 1104 1.22 1190 1.35
.99 914 1.05 950 1.12 984 1.19 1019 1.26 1054 1.32 1134 1.49 1213 1.64
2
.99 1025 1.03 1065 1.08 1107 1.12 1153 1.17 1200 1.21
1 HP Standard Motor & Sheaves
.80 916 .85 952 .89 988 .92 1025 .96 1058 .99 1142 1.05 1226 1.10
2 HP Oversized Motor & Sheaves
External Static Pressure (Inches of Water)
.20
.30
.40
.50
2
1 HP Standard Motor
2 HP Oversize Motor & Sheaves
39
6¼, , , , , 7½ Ton
Standard Efficiency
.60
.70
.80
.90
1 HP Standard Motor & Sheaves
2 HP Oversized Motor & Sheaves
2HP Standard Motor & Sheaves
.60
.70
.80
.90
2 HP Standard Motor & Sheaves
1.00
1.25
1.50
1.00
1.25
1.50

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents