Performance Data 10, 12½ Ton High Efficiency - Trane Voyager Manual

Product
Table of Contents

Advertisement

Table 49-1
Evaporator Fan Performance 10 Ton YCH121C
.10
.20
.30
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Field
Supplied Low Static Drive (1)
3200
— 419 0.53 457 0.62 494 0.73 528 0.83 563 0.95 595 1.07 627 1.20 656 1.32 685 1.45 712 1.58 739 1.72
3600
416 0.60 452 0.70 487 0.80 521 0.91 553 1.03 584 1.15 615 1.27 645 1.41 674 1.55 702 1.69 728 1.82 754 1.97
4000
454 0.80 487 0.90 520 1.01 550 1.13 580 1.25 610 1.38 638 1.51 666 1.65 693 1.80 720 1.95 746 2.10 771 2.26
4400
492 1.03 524 1.15 553 1.27 582 1.40 610 1.52 637 1.65 664 1.80 690 1.95 715 2.09 740 2.25 765 2.41 789 2.57
4800
531 1.31 561 1.44 588 1.57 615 1.70 641 1.85 666 1.98 691 2.12 716 2.28 740 2.44 764 2.60 787 2.76 810 2.93
For Standard Evaporator Fan Speed (RPM), reference Table 53-1.
For Standard Motor & High Static Drive Accessory/Fan Speed (RPM), reference Table 53-2.
For Oversize Evaporator Fan Speed (RPM), reference Table 53-3.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to filters and wet coils.
Fan motor heat (MBH) = 3.15 x Fan Bhp.
1. Field Supplied Fan Sheave AK89 required. Field Supplied Belt
may be necessary.
2. 3 HP Oversize Motor with Field Supplied Fan Sheave BK85 Required.
Field Supplied Belt may be necessary.
Table 49-2
Evaporator Fan Performance 12½ Ton YCD151C
.10
.20
.30
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field
Supplied Low Static Drive (1)
4000
— 497 0.75 551 0.92 598 1.08 641 1.23 680 1.38
4500
— 531 0.96 583 1.16 629 1.34 671 1.52 709 1.70
5000
506 0.98 565 1.21 616 1.43 661 1.65 701 1.85 739 2.05
5500
544 1.24 600 1.51 649 1.76 693 2.00 733 2.23 770 2.45
6000
582 1.55 636 1.84 684 2.12 726 2.39 765 2.65 801 2.90
For Standard Evaporator Fan Speed (RPM), reference Table 53-1.
For Standard Motor & High Static Drive Accessory/Fan Speed (RPM), reference Table 53-2.
For Oversize Evaporator Fan Speed (RPM), reference Table 53-3.
NOTES:
NOTES:
NOTES:
NOTES:
NOTES:
Data includes pressure drop due to filters and wet coils.
Fan motor heat (MBH) = 3.15 x Fan Bhp.
1. Field Supplied Fan Sheave BK115 required. Field Supplied Belt
may be necessary.
Indicates both downflow and horizontal units.
Performance
Data
External Static Pressure (Inches of Water)
.40
.50
.60
2 HP Standard Motor & Drive
Trane's factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our product's warranty will not
be affected.
Table 49-1 (Continued)
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static Drive Accessory
3200
791 2.01 816 2.17 840 2.32 864 2.48 886 2.64 908 2.80
3600
803 2.26 827 2.41 851 2.58 874 2.74 897 2.91 919 3.08
4000
819 2.57 842 2.72 864 2.89 886 3.05 908 3.22 929 3.40
4400
836 2.91 859 3.08 881 3.25 902 3.43 —
4800
855 3.29
External Static Pressure (Inches of Water)
.40
.50
.60
.70
3 HP Standard Motor & Drive
716 1.53 750 1.67 782 1.82 812 1.96 841 2.09 869 2.23 896 2.36
745 1.87 778 2.03 810 2.20 840 2.36 869 2.52 896 2.68 923 2.84
774 2.25 807 2.44 838 2.63 868 2.81 897 2.99 924 3.17 950 3.35
804 2.67 837 2.89 868 3.10 897 3.31 925 3.52 952 3.72 978 3.92
835 3.15 867 3.39 898 3.63 927 3.86 955 4.09 981 4.32 1007 4.54
3 HP Standard Motor & Drive
Table 49-2 (Continued)
1.40
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4000
922 2.50 947 2.63 971 2.76 994 2.89 1016 3.04 1037 3.19 1059 3.35
4500
948 2.99 973 3.14 997 3.30 1020 3.45 1043 3.60 1065 3.75 1087 3.89
5000
976 3.53 1000 3.71 1024 3.88 1047 4.05 1070 4.22 1092 4.39 1113 4.56
5500
1004 4.12 1028 4.32 1052 4.51 1075 4.71 1097 4.90 1119 5.09 1140 5.28
6000
1032 4.77 1056 4.99 1080 5.21 1103 5.42 1125 5.64 —
49
10, 12½ Ton
High Efficiency
.70
.80
.90
1.00
2 HP Standard Motor & Drive
3 HP Oversize Motor & Field
Supplied Drive (2)
External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
2 HP Standard Motor and
.80
.90
1.00
5 HP Oversize Motor & Drive
Trane's factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or premature motor failure. Our
product's warranty will not be affected.
External Static Pressure (Inches of Water)
1.50
1.60
1.70
3 HP Standard Motor & High Static Drive Accessory
5 HP Oversize Motor & Drive
1.10
1.20
1.30
766 1.86
779 2.11
795 2.41
813 2.74
833 3.11
3 HP Oversize
Motor and Drive
1.80
1.90
2.00
3 HP Oversize Motor
and Drive
929 2.97
940 3.26
1.10
1.20
1.30
3 HP Standard
Motor & High Static
Drive Accy
1.80
1.90
2.00

Hide quick links:

Advertisement

Table of Contents
loading