Network Errors - Omron CS1W-PRM21 Operation Manual

Sysmac cs/cs series
Hide thumbs Also See for CS1W-PRM21:
Table of Contents

Advertisement

Troubleshooting Using LED Indicators
7-2-5

Network Errors

Network Errors
BST
COMM
BF
Not lit
Not lit
Not lit
Lit
Lit
Not lit
Lit
Network errors are errors which occur when attempting to startup a network,
i.e. the PROFIBUS-DP Master Unit has been switched to CLEAR or OPER-
ATE mode. The Unit will parameterize the slave stations and start data
exchange. An error in this process can be determined by examining the BST,
COMM and BF LED indicators.
The error determination procedure uses the table below. To determine the
error
• First find the status of the BST LED indicator (left column).
• Move one column to the right and find the COMM LED indicator status.
• Move one column to the right and find the BF LED indicator status.
The probable error causes are then listed to the right of the third column.
Probable cause
The PROFIBUS-DP Master Unit is in
OFFLINE or STOP mode. No communica-
tion over the network.
A hardware error has occurred in the
PROFIBUS interface of the Unit, or a Mas-
ter station has been detected beyond the
Highest Station Address. The Unit has
switched to OFFLINE.
This indicates faulty wiring, broken mes-
sage, short-circuits, or faulty bus timings.
A protocol error has occurred in the PROFI-
BUS interface of the Unit, the Unit has
switched to OFFLINE.
This indicates lost tokens, or an active sta-
tion detected beyond the Highest Station
Address setting (HSA).
A Double-Address error has occurred on
the network, i.e. there is a second Master
Unit with the same PROFIBUS address on
the network. the Unit has switched to
OFFLINE.
Not a valid combination.
Not a valid combination.
Correction
Switch the Unit to either CLEAR or OPER-
ATE mode.
• Check the network wiring, and make sure
it is correct (not too long, long stub lines,
etc.)
• Check for short-circuits.
• Check the bus timing set in CX-Profibus.
• Check if any other faulty devices are on
the same network.
• Switch the Unit to CLEAR / OPERATE
mode again.
• Check the network wiring, and other
Master devices on the network. Make
sure they are all correct.
• Check the HSA setting in the DTM's Bus
Parameter tab. Set it to the highest mas-
ter address which is on the network.
• Check if any other faulty devices are on
the same network.
• Switch the Unit to CLEAR / OPERATE
mode again.
• Check the Master devices on the net-
work. Make sure they all have unique net-
work addresses.
• After correction, switch the Unit to
CLEAR / OPERATE mode again.
Section 7-2
133