Unit Components
DM Area Allocations
2-1-4
PROFIBUS Connector
9
6
Unit No.
(decimal)
0 (0)
D30000 to D30099
1 (1)
D30100 to D30199
2 (2)
D30200 to D30299
3 (3)
D30300 to D30399
4 (4)
D30400 to D30499
5 (5)
D30500 to D30599
6 (6)
D30600 to D30699
7 (7)
D30700 to D30799
The PROFIBUS connector on the font of the Unit is a 9-pin female sub-D con-
nector, as recommended by the PROFIBUS standard EN 50170.
Pin No.
Signal
1
Shield
5
2
--
3
RxD/TxD-P
4
RTS
5
DGND
6
VP
7
--
1
8
RxD/TxD-N Receive/Transmit data - minus (A wire)
9
-
The signal RTS (TTL signal) is for the direction control of repeaters, which do
not have a self-controlling capability.
The signals DGND and VP are used to power the bus terminator located in
the cable connector.
Note The orientation of the sub-D connector allows the use of PROFIBUS connec-
tors with a 90° angle cable outlet, e.g ERNI, Delconec and Phoenix.
Note The 9-pin sub-D connector uses #4/40 UNC thread, for mechanical fixation of
the cable connector. Make sure that if non-standard PROFIBUS connectors
are used, the corresponding thread is used on the cable connector.
Allocated words
Unit No.
(decimal)
8 (8)
9 (9)
A (10)
B (11)
C (12)
D (13)
E (14)
F (15)
Shield/protective ground
Receive/Transmit data - plus (B wire)
Control signal for repeaters (direction control) (TTL)
Data ground (reference potential for VP)
Supply voltage of the terminator resistance (5 Vdc)
-
Section 2-1
Allocated words
D30800 to D30899
D30900 to D30999
D31000 to D31099
D31100 to D31199
D31200 to D31299
D31300 to D31399
D31400 to D31499
D31500 to D31599
Description