Defining And Changing I/O Mapping - Omron CS1W-PRM21 Operation Manual

Sysmac cs/cs series
Hide thumbs Also See for CS1W-PRM21:
Table of Contents

Advertisement

Configuring the Master
Example
Example
6-4-3

Defining and Changing I/O Mapping

Example
122
The Bus Parameter tab as used in the example is shown below.
The baud rate has been set to 1500 kBit/s. Given the amount of slaves and
the amount of I/O data, this results in a poll cycle time of approximately 3.8 ms
(Min Slave Interval).
After making the changes, select the Save button in the lower right corner of
the User Interface to accept the changes. Next select the Slave Area tab to
display the I/O Mapping.
The I/O data of all slaves can be mapped on to the PLC Memory Areas.
through two Output Ares and two Input Areas. The Output data can be distrib-
uted over two Output Areas, each of which can be mapped on to PLC Mem-
ory. Similarly, the Input data can be distributed over two Input Areas, each of
which can be mapped on to PLC Memory.
The figure below shows the Master DTM's Slave Area tab for the example net-
work.