Bit
Name
05
Diag.Invalid_Slave_Response
06
Diag.Prm_Fault
07
Diag.Master_Lock
Slave Diagnostics Byte 2
A layout of Byte 2 is shown below. This byte is mapped to the low-byte of Word D.
Bit
Name
00
Diag.Prm_Req
01
Diag.Stat_Diag
02
Reserved
03
Diag.WD_On
04
Diag.Freeze_Mode
05
Diag.Sync_Mode
06
Reserved
07
Diag.Deactivated
This bit is set by the Master Unit if the slave has returned an invalid response to a
Master request message. The slave station will set this bit to 0.
Set by the slave station, this bit indicates that the last received parameter data
from the Master Unit have been rejected. The parameter data in the slave station
differ from the parameter sent by the Master Unit.
This bit indicates that the slave station has been parameterized by another mas-
ter. The bit is set by the Master Unit, if the address in byte 4 differs from 255 and
from the Master Unit's own address. The slave station sets this bit to zero.
7 6 5 4 3 2 1 0
Byte 2
This bit is set by the slave station and indicates that it needs to be (re-)aparame-
terized. The slave station is not in Data_Exchange with the Master Unit. The bit
remains on as long as it has not been parameterized successfully.
This bit indicates static diagnostics at the slave station. The Master unit will
repeatedly request diagnostics data. As long as this bit is set, Data_Exchange
with the Master Unit is not being performed.
This bit is reserved and always set to 1 by the slave station.
If the watchdog has been enabled at the slave station (through the appropriate
setting in the parameterization message) this bit will be set.
If the slave station has been set to the Freeze mode, using the global command,
this bit will be set to on. The bit will be set to off, if an Unfreeze command has
been received.
If the slave station has been set to the Sync mode, using the global command,
this bit will be set to on. The bit will be set to off, if an Unsync command has been
received.
This bit is reserved.
This bit is set by the Master Unit, indicating that the slave station has been dis-
abled (i.e. using the STOP FINS command). The slave station is allocated to the
Master Unit, but removed from cyclic processing.
Description
Diag.Prm_Req
Diag.Stat_Diag
Reserved
Diag.WD_On
Diag.Freeze_Mode
Diag.Sync_Mode
Diag.Deactivated
Description
Appendix