Error Transferring The Data Record - Siemens 6ES7141-6BG00-0BB0 Equipment Manual

I/o device digital inputs di 8x24vdc m12-l 8xm12
Table of Contents

Advertisement

Parameter data record
B.3 Error transferring the data record
B.3

Error transferring the data record

Error transferring the data record
The I/O device checks the values of the transferred data record. Only if the values were
transferred without errors does the I/O device apply the values from the data record.
The "WRREC" instruction for writing data records returns corresponding error codes in the
"STATUS" parameter when errors occur. For STEP 7 you will also find the parameter
description in the STEP 7 online help.
The Error codes table shows the following:
• The specific error codes of the I/O device
• The meaning of the error code
• A suggestion for correcting the error
• The data record at which the error may occur
Table B-1  Error codes
Error code in STATUS parameter
(hexadecimal)
Byte 0 Byte 1 Byte 2 Byte 3
DF
80
B0
DF
80
B1
DF
80
B2
DF
80
E0
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
66
Meaning
xx
Number of the data record unknown.
xx
Length of the data record incorrect.
xx
I/O device cannot be accessed:
xx
Wrong version or error in the header
information.
01
Reserved bit set
02
Invalid diagnostics enable bit set for
operating mode.
07
Invalid coding for replacement filter
time.
11
Invalid measuring range set.
Solution
Enter a valid number for the data
record.
Enter a valid value for the data record
length.
Check the assigned values for the para­
meters of the "WRREC" instruction.
Correct the version, length and number
of parameter blocks.
Check the parameters of the I/O device.
Check the parameters of the I/O device.
Check the parameters of the I/O device.
Check the parameters of the I/O device.