B.3

Error transferring the data record

Error transferring the data record
The I/O device checks the values of the transferred data record. Only if the values were
transferred without errors does the I/O device apply the values from the data record.
The "WRREC" instruction for writing data records returns corresponding error codes in the
"STATUS" parameter when errors occur. For STEP 7 you will also find the parameter
description in the STEP 7 online help.
The Error codes table shows the following:
• The specific error codes of the I/O device
• The meaning of the error code
• A suggestion for correcting the error
• The data record at which the error may occur
Table B-1  Error codes
Error code in STATUS parameter
(hexadecimal)
Byte 0 Byte 1 Byte 2 Byte 3
DF
80
B0
DF
80
B1
DF
80
B2
DF
80
E0
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
I/O device digital outputs DQ 8x24VDC/0.5A M12-L 8xM12 (6ES7142-6BG00-0BB0)
Equipment Manual, 03/2023, A5E46570894-AD
Meaning
xx
Number of the data record unknown.
xx
Length of the data record incorrect.
xx
I/O device cannot be accessed:
xx
Wrong version or error in the header
information.
01
Reserved bit set
02
Invalid diagnostics enable bit set for
operating mode.
06
Invalid coding for substitute value reac­
tion.
11
Invalid output range set.
Parameter data record
B.3 Error transferring the data record
Solution
Enter a valid number for the data
record.
Enter a valid value for the data record
length.
Check the assigned values for the para­
meters of the "WRREC" instruction.
Correct the version, length and number
of parameter blocks.
Check the parameters of the I/O device.
Check the parameters of the I/O device.
Check the parameters of the I/O device.
Check the parameters of the I/O device.