Unused Channel Setting

When no temperature sensor is connected to a channel, the temperature control module performs upscale processing for the
channel. Therefore, when no temperature sensor has not been connected to a channel where no temperature control is to be
performed, the module determines that the temperature process value (PV) has exceeded the temperature measuring range
for the input range, and the ALM LED blinks.
Setting unused channels can prevent faulty alert detection because the PID control, temperature judgment, and alert
judgment are not executed on the set channels.
Setting method
Set a value in "Unused channel setting" of "Control basic parameters" of "Application Setting". The following table shows the
relation between each setting value and control status.
Setting value
Used (0)
Unused (1)
Setting unused channels does not change the sampling cycle.
Control status
PID control
Performed (However, it depends on other setting status.)
Not performed
Temperature judgment
6 INSTALLATION AND WIRING
Alert judgment
6.5 Unused Channel Setting
6
49