External Wiring; R60Tctrt2Tt2 - Mitsubishi MELSEC iQ-R series User Manual

Temperature control module
Table of Contents

Advertisement

6.3

External Wiring

The following figure shows the external wiring.

R60TCTRT2TT2

Standard control
*2
·
*2
*1
Controlled
object
·
*1
*1 Use the shielded compensation lead wire.
*2 Use the shielded cable.
Use the compensation lead wire for the cable of a thermocouple. The shielded cable cannot be used. If the
compensation lead wire is not used, and when the cold junction temperature compensation resistor (1) is
away from the end tip (2) of a thermocouple, the (ambient) temperature (3) difference may lead to a faulty
temperature process value (PV).
6 INSTALLATION AND WIRING
38
6.3 External Wiring
R60TCTRT2TT2
L1
L2
L4
COM-
24VDC
Filter
CH1+
CH1-
Filter
CH2+
CH2-
Filter
CH4+
CH4-
(2)
(3)
Internal
circuit
·
Internal
circuit
Internal
circuit
R60TCTRT2TT2(BW)
(1)

Advertisement