Technical data
6.2 Electrical Data
SINAMICS G120 Power Module
Table 6-10
Feature
Line operating voltage &
power ranges
Input frequency
Output frequency
cos φ
Inverter efficiency
Overload capability (HO)
Overload capability (LO)
Inrush current
Pulse frequency
Electromagnetic
compatibility
Braking
Protection level
Temperature range
Storage temperature
Humidity
Operational altitude
Protection features
Standards
CE marked
6-12
Performance ratings
Specification
3 AC 380 V ... 480 V ± 10 %
High Overload: 0.37 kW ... 75 kW (0.50 hp ... 100.0 hp)
Light Overload: 2.2 kW ... 75 kW (3.0 hp ... 100.0 hp)
47 Hz ... 63 Hz
0 Hz ... 650 Hz
0.95
95 % ... 97 %
1.5 x Nominal output current (150 % overload) for 57 s every 300 s
2 x Nominal output current (200 % overload) for 3 s every 300 s
1.1 x Nominal output current (110 % overload) for 57 s every 300 s
1.5 x Nominal output current (150 % overload) for 3 s every 300 s
Less than rated input current
4 kHz (standard); 4 kHz ... 16 kHz (in 2 kHz steps)
Optional Class A filters available according to EN 55011
DC braking, Compound braking, Dynamic braking with integrated chopper
(braking functionality depends on the type of CU and PM)
IP20
0 °C ... +50 °C (32 °F ... 122 °F) - High Overload (HO)
0 °C ... +40 °C (32 °F ... 104 °F) - Light Overload (LO)
-40 °C ... +70 °C (-40 °F ... 158 °F)
< 95% RH - non-condensing
Up to 1000 m (3280 ft) above sea level without derating
Undervoltage, Overvoltage, Overload, Ground faults, Short circuit, Stall
prevention, Motor blocking protection, Motor overtemperature, Power
Module overtemperature, Parameter interlock
UL, cUL, CE, C-tick
Conformity with EC Low Voltage Directive 73/23/EEC and filtered
versions also Electromagnetic Compatibility Directive 89/336/EEC
Hardware Installation Manual, 2006-04-04, A5E00807525B AA