Technical data
6.1 Mechanical Data
Figure 6-1
Humidity range
Relative air humidity for the SINAMICS G120 Power Module is ≤ 95 % non-condensing.
In areas of high relative humidity, measures should be taken to ensure that condensation
does not form within or around the SINAMICS G120 Power Module. Anti-condensation
heaters are commonly used to prevent the formation of condensation.
Altitude
If the SINAMICS G120 Power Module is to be installed at an altitude greater than 1000 m
(3280 ft) derating will be required. The figure below shows the derating required in
accordance with altitude.
Figure 6-2
Shock and vibration
Do not drop the SINAMICS G120 Power Module or expose to sudden shock. Do not install
the SINAMICS G120 Power Module in an area where it is likely to be exposed to constant
vibration.
Electromagnetic radiation
Do not install the SINAMICS G120 Power Module near sources of electromagnetic radiation.
6-2
Power derating for temperature
Derating for altitude
Hardware Installation Manual, 2006-04-04, A5E00807525B AA
Power Modules PM240