Cable Entry - Siemens FDOOTC241 Technical Manual

Neural fire detector
Hide thumbs Also See for FDOOTC241:
Table of Contents

Advertisement

5.13 Cable entry

1
2
!
30°
1 The conductor loops must be placed flat in the base bottom.
2 The conductor loops must not be placed over this zone, as
otherwise the detector cannot be inserted correctly.
3 Screwless connection terminals
4 Bare length 6.5...7.5 mm
Building Technologies
Fire Safety
The detector bases contain a terminal block. Permissible conductor cross-section
0.28...1.5 mm².
Note the positive and negative poles.
Only connect one wire per terminal. This is the only way to ensure the connection
is failure-free for the entire service life of the device.
7
Figure 23: Cable entry in detector base
3
4
5
Contact for test tips
6
Turn the screwdriver 90° in the direction of the arrow to remove
the conductor or insert a strand.
7
Optimum insertion of the wire without tool, at an angle of
approx. 30°
Mounting / Installation
Cable entry
5
6
77 | 94
A6V10209291_h_en_--
2016-03-03
5