3.3.9 Renovation mode

3.3.10 Test mode

Building Technologies
Fire Safety
When operating the point detectors on the FDnet, individual detectors can be set
specifically to renovation mode on the fire control panel.
Select renovation mode if major work is being carried out in the room and large
volumes of dust or aerosols are being produced.
NOTICE
Changed settings
Limited alarm functions in renovation mode.
In renovation mode, the neural fire detector and the heat detector only trigger
alarm when the temperature exceeds 80 °C for 20 seconds.
The wide-spectrum smoke detector does not trigger an alarm in renovation
mode. All other functions continue to work as normal.
For testing purposes the detector can be set to test mode. In test mode the
detector reacts faster and with a higher sensitivity level. The detector can be tested
with the detector exchanger and tester FDUD292 or the intelligent detector tester
FDUD293.
Electronic testing:
The detector can be tested with the detector exchanger and tester FDUD292 or the
intelligent detector tester FDUD293.
You will find more information in documents 007227 and 009718.
Physical testing:
The optical function part on the neural fire detector can also be tested with the
test gas REF 8 or REF 8-S.
The heat sensors of the neural fire detector can be tested with a hot air fan.
The CO sensor can be tested with the test gas REF 8-C.