5.14 Detector lines

5.14.1 Connection diagram
5.14.1.1 Use of unshielded cables
Building Technologies
Fire Safety
General cabling information
Preferably, twisted and non-shielded cables should be used. This also applies
to connecting the external alarm indicators.
Shielded cables are only required in special cases, such as strong high-
frequency fields.
The following applies to FDnet detector lines:
Loops, stubs and T-branches are possible.
You may only connect external alarm indicators to one detector.
The connection is established from base to base using twisted or non-twisted wire
pairs.
-
+
-
-
-
+
+
+
1
+
-
3
-
+
Figure 25: Connection diagram for addressed detector line with and without external alarm indicators
(without shielded cables)
1 Control panel
2 Detector bases FDB221/FDB221-AA,
FDB222
-
-
2
+
+
+
LINE
-
-
+
+
+
4
3 Auxiliary terminals DBZ1190-xx
4 External alarm indicator
Mounting / Installation
Detector lines
-
-
-
+
+
+
4
-
-
-
+
+
2
A6V10209291_h_en_--
2016-03-03
5
-