Installation

4.6 Installing the interface module

4.6
Installing the interface module
Introduction
The interface module connects the ET 200MP with the PROFINET IO/PROFIBUS DP and
exchanges data between the higher-level controller and the I/O modules.
Requirements
The mounting rail is installed.
In a system power supply located before the interface module, a U connector is inserted on
the back right.
Tools required
Screwdriver with 4.5 mm blade
Installing the interface module
Watch video sequence
(http://cache.automation.siemens.com/media/67462859_installing_web_en/start.htm)
To install an interface module, proceed as follows:
1. Mount the U-connector on the back right-hand side of the interface module.
2. Hook the interface module on the rail.
3. Pivot the interface module towards the back.
4. Tighten the screw for the interface module (torque 1.5 Nm).
Figure 4-7
48
Installing the interface module
Automation system
System Manual, 12/2014, A5E03461182-AC