Operation On Grounded Infeed - Siemens SIMATIC S7-1500 System Manual

Automation system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

5.2

Operation on grounded infeed

Introduction
Information is provided below on the overall configuration of an S7-1500 automation
system/ET 200MP distributed I/O system on a grounded infeed (TN-S system). The specific
subjects discussed are:
● Disconnecting devices, short-circuit and overload protection to IEC 60364 (corresponding
to DIN VDE 0100) and IEC 60204 (corresponding to DIN VDE 0113)
● Load power supplies and load circuits
Grounded infeed
In the case of grounding incoming supplies (TN-S system) the neutral conductor (N) and the
protective conductor (PE) are each grounded. Both conductors form a part of the overvoltage
concept. When a plant is in operation, the current flows across the neutral conductor. When
a fault occurs, for example a single ground fault between a live conductor and ground, the
current flows through the protective conductor.
Safe galvanic isolation (SELV/PELV in accordance with IEC 60364-4-41)
Load current supplies/system power supplies with safe galvanic isolation are required for the
operation of the S7-1500 automation system/ET 200MP distributed I/O system. This
protection is designated as SELV (Safety Extra Low Voltage)/PELV (Protective Extra Low
Voltage) in accordance with IEC 60364-4-41.
Reference potential of the controller
The reference potential of the S7-1500 automation system/ ET 200MP distributed I/O system
is connected with the mounting rail through a high-resistance RC combination in the
CPU/interface module. In this way, high-frequency interference currents are conducted and
electrostatic charges are avoided. Despite the grounded mounting rail, the reference
potential of the S7-1500 automation system/ET 200MP distributed I/O system has to be
considered as ungrounded due to the high-resistance connection.
If you want to configure the S7-1500 automation system/ET 200MP distributed I/O system
with grounded reference potential, connect the M connection of the CPU/interface module
galvanically with the protective conductor.
You can find a simplified representation of the potential relationships in section Electrical
configuration (Page 56).
Automation system
System Manual, 12/2014, A5E03461182-AC
5.2 Operation on grounded infeed
Wiring
53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et 200mp

Table of Contents