5.5

Connecting the supply voltage

Introduction
The supply voltage of the CPU/interface module is supplied by means of a 4-pole connection
plug, which is located on the front of the CPU.
Connection for supply voltage (X80)
The connections of the 4-pole connector have the following meaning:
Figure 5-5
The maximum connector cross-section is 1.5 mm
of looping the supply voltage uninterrupted, even when it is unplugged.
Requirements
● Only wire the cable connector when the supply voltage is turned off.
● Follow the wiring rules (Page 59).
Tools required
3 to 3.5 mm screwdriver
Tool-free connection of cables: multi-wire (stranded), with end sleeve or ultrasonic compressed
To connect a wire without tools, follow these steps:
1. Strip 8 to 11 mm of the wires.
2. Seal or crimp the wire with end sleeves.
3. Insert the wire into the push-in terminal as far as it will go.
4. Push the wired connector into the socket of the CPU/interface module.
Automation system
System Manual, 12/2014, A5E03461182-AC
+ 24 V DC of the supply voltage
Mass of the supply voltage
Mass of the supply voltage for looping (current limited to 10 A)
+ 24 V DC of the supply voltage for looping (current limited to 10 A)
Spring opener (one spring opener per terminal)
Connection for supply voltage
5.5 Connecting the supply voltage
. The cable connector offers you the option
2
Wiring
61