Feedback Data Record Of The Et 200Mp Distributed I/O System - Siemens SIMATIC S7-1500 System Manual

Automation system
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Flexible automation concepts
9.2 Configuration control
9.2.4

Feedback data record of the ET 200MP distributed I/O system

Operating principle
The feedback data record informs you about the accuracy of the module assignment and
gives you the option of detecting assignment errors in the control data record. The feedback
data record is mapped by means of a separate data record 197.
Slot assignment
The feedback data record exists only when configuration control is configured and always
refers to the maximum quantity framework without interface module, i.e., 31 slots.
The following table shows the slot assignment of the modules:
Table 9- 7
Slot assignment
Slot
Modules
0
System power supply (optional)
2 - 31
I/O modules/system power supplies, depending on the station option
Partial reading of the feedback data record is possible.
132
Comment
Upstream from interface module
Downstream from the interface module
Automation system
System Manual, 12/2014, A5E03461182-AC