Home screen: Chiller status information
The home screen
(Table
19) provides the most frequently
needed chiller status information on "touch targets" (the
entire white rectangular areas) for each chiller component.
Touching any touch target displays a screen containing
more chiller status information related to each
component.
Figure 19. Main screen
Table 17.
Main screen items
Description
Active Chilled Water Setpoint
Active Current Limit Setpoint
Average Motor Current %RLA
Evap Entering/Leaving Water Temp
Cond Entering/Leaving Water Temp
Frequency Command
Evaporator Water Flow Status
Condenser Water Flow Status

Viewing Chiller Operating Modes

On the Reports screen, touch Chiller Operating Modes to
view the current operating status of the chiller in terms of
the top-level operating mode and submodes.
Table 18.
Operating modes
Chiller Modes
MP Resetting
Stopped
Local Stop
Immediate Stop
No Circuits Available
Diagnostic Shutdown – Manual Reset The chiller has been shut down on a latching diagnostic that requires manual intervention to reset.
Chilled Water Control
Starting is Inhibited by Low Ambient
Temperature
RTAF-SVX001A-EN
Resolution
Units
X.X
°F /°C
X.X
%RLA
X.X
%RLA
X.X
°F /°C
X.X
°F /°C
X.X
Hz
X.X
Description
The main processor is going through reset
No chiller sub-modes.
The chiller is not running either circuit and cannot run without intervention. Further
information is provided by the sub-mode:
Chiller is stopped by TD7 Stop button command– cannot be remotely overridden.
Chiller is stopped by the TD7 Panic Stop (by pressing Stop then Immediate Stop in succession) – previous
shutdown was manually commanded to shutdown immediately.
The entire chiller is stopped by circuit diagnostics or lockouts that may automatically clear.
Chiller is running to provide a chilled water temperature per the active chilled water setpoint (may be as
arbitrated from various sources). (For cooling only units, this mode may be suppressed.)
The chiller is inhibited based on the outdoor air temperature.
Note: You can also access the Chiller Operating Modes
screen from the chiller status button in the upper
left corner of the screen.
Figure 20. Chiller operating modes