Trane Sintesis RTAF Installation, Operation And Maintenance Manual page 83

Air-cooled chillers
Table of Contents

Advertisement

Table 28.
Communications diagnostics (continued)
Affects
Diagnostic Name
Target Severity
Comm Loss: Heat
Recovery Leaving Water
Temperature Sensor
Comm Loss: HR Leaving
Chiller
Water Temp Sensor
Comm: HR Leaving Water
Temp
Comm Loss: High
Pressure Cutout Switch -
xy
Comm Loss: High
Cprsr
Pressure Cutout Sw - xy
Comm: High Pres Cutout
Sw - xy
Comm Loss: Liquid Line
Temperature
Circuit
Comm: Liquid Line Temp
Comm Loss: Local BAS
Interface
Chiller
Comm: Local BAS
Interface
Comm Loss: Motor RLA
Input - xA
Cprsr
Comm: Motor RLA Input -
xA
Comm Loss: Motor
Winding Thermostat
Compressor 1A
Comm Loss: Motor
Circuit
Winding Tstat Cprsr 1A
Comm: Motor Tstat Cprsr
1A
Comm Loss: Motor
Winding Thermostat
Compressor 2A
Comm Loss: Motor
Circuit
Winding Tstat Cprsr 2A
Comm: Motor Tstat Cprsr
2A
Comm Loss: Oil Loss Level
Sensor Input
Comm Loss: Oil Loss Level
Circuit
Sensor Input
Comm: Oil Level Sensor
Comm Loss: Oil Pressure -
xy
Cprsr
Comm: Oil Pressure - xy
Comm Loss: Oil Return
Line Solenoid Valve -xy
Comm Loss: Oil Return
Cprsr
Solenoid Valve - xy
Comm: Oil Ret Sol Vlv xy
Comm Loss: Outdoor Air
Temperature
Chiller
Comm: Outdoor Air Temp
Comm Loss:
Programmable Relay
Board 1
None
Comm: Program Relay
Board 1
RTAF-SVX001A-EN
Active
Modes
[Inactive
Persistence
Modes]
Info
Latch
All
Normal
Latch
All
Normal
Latch
All
Info
NonLatch
All
Normal
Latch
All
Normal
Latch
All
Normal
Latch
All
Normal
Latch
All
Immediate Latch
All
Normal
Latch
All
Normal
Latch
All
Info
Latch
All
Criteria
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period Note: The
Subcooled Liquid Line Temperature Sensors are used for
determination of charge and accurate tonnage predictions
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Use last valid BAS setpoints.
Diagnostic is cleared when successful communication is
established with the LonTalk LLID (LCIC) or BacNet LLID
(BCIC).
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Diagnostics
Reset
Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
83