Trane Sintesis RTAF Installation, Operation And Maintenance Manual page 65

Air-cooled chillers
Table of Contents

Advertisement

2. Use a soft brush or vacuum to remove base debris or
surface loaded fibers from both sides of the coil.
Note: When possible, clean the coil from the opposite
direction of normal air flow (inside of unit out) to
push debris out.
3. Using a sprayer and water ONLY, clean the coil
following the guidelines below.
a. Sprayer nozzle pressure should not exceed 580 psi.
b. The maximum source angle should not exceed 25°
to the face of the coil. See
spray the microchannel perpendicular to face of the
coil.
c. Spray nozzle should be approximately 1"-3" from
the coil surface.
d. Use at least a 15º fan type of spray nozzle.
Figure 54. Sprayer source angle
Note: To avoid damage from the spray wand contacting
the coil, make sure the 90º attachment does not
come in contact with the tube and fin as abrasion to
the coil could result.
RTAF-SVX001A-EN
Figure
54. For best results
Maintenance
65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents