Trane Sintesis RTAF Installation, Operation And Maintenance Manual page 84

Air-cooled chillers
Table of Contents

Advertisement

Diagnostics
Table 28.
Communications diagnostics (continued)
Affects
Diagnostic Name
Target Severity
Comm Loss:
Programmable Relay
Board 2
None
Comm: Program Relay
Board 2
Comm Loss: Slide Valve
Load - xy
Cprsr
Comm: Slide Valve Load -
xy
Comm Loss: Slide Valve
Unload - xy
Cprsr
Comm: Slide Valve
Unload - xy
Comm Loss: Speed
Command - xA
Cprsr
Comm: Speed Command
-xA
Comm Loss: Starter xy
Cprsr
Comm Loss: Step Load -
xy
Cprsr
Comm: Step Load - xy
Comm Loss: Suction
Refrigerant Pressure - xy
Comm Loss: Suction Rfgt
Cprsr
Pressure - xy
Comm: Suction Rfgt Press
xy
Comm Loss: Water
System Differential
Pressure
Comm Loss: Water
Chiller
System Diff Pressure
Comm: Water Sys Diff
Press
84
Active
Modes
[Inactive
Persistence
Modes]
Info
Latch
All
Normal
Latch
All
Normal
Latch
All
Normal
Latch
All
Immediate Latch
All
Normal
Latch
All
All [Ckt/
Immediate Latch
Cprsr lock
out]
Info
Latch
All
Criteria
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 15-30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Reset
Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote