Location 252: Telephone Line Fault Monitor
Location 252 is used to program the telephone line monitor. Select a number from the table below which
corresponds to the activation required for your installation. Factory default is "0" and this feature is not enabled.
NOTE: When using a phone line monitor, it is suggested that a delay be programmed into location 253 to delay
alarm activation upon phone line fault. This could eliminate the possibility of a false alarm being created due to
phone line maintenance performed by the telephone company, which many times is performed during late night or
early morning hours.
VALUE
"0"
"1"
"3"
"5"
"7"
"9"
"11"
"13"
"15"
Location 253: Delay of Alarm Activation For Telephone Line Fault
The number programmed in this location determines the amount of time the Ranger 9000E will delay the alarm
activation selected in location 252. This delay is programmable in 10 second increments from 10 to 150 seconds.
Possible delay values are "1" ("1" x 10 seconds = 10 second delay) through "15" ( "15" x 10 seconds = 150 second
delay). Factory default is "0", no delay.
Location 254: Dynamic Battery Test Time
The number programmed in location 254 determines when the control will perform a dynamic battery test. This time
is programmable in two hour increments from 12:00 AM to 10:00 PM. Possible values for this location are "0" thru
"11". Factory default is "3" (3 x 2 = 6) meaning the dynamic battery test will occur at 6:00 AM. Programming a "0"
(0 x 2 = 0) in this location would set the test time for 00:00 (midnight). Programming a "11" (11 x 2 = 22) in this
location would set the test time for 22:00 (10:00 PM).
Location 255: Dynamic Battery Test Duration
The number programmed in location 255 will determine the number of minutes the Ranger 9000E will go into the
dynamic battery test mode during each 24 hour period. This test causes the control to function with the system
battery, thus verifying that the battery is capable of performing as designed during an actual power failure. Factory
default is "0" and this feature is not enabled.
DISABLED
ENABLED - SILENT MODE
ENABLED - ACTIVATE SIREN ONLY
ENABLED - ACTIVATE KEYPAD SOUNDER ONLY
ENABLED - ACTIVATE SIREN & KEYPAD SOUNDER
ENABLED - SILENT MODE (ARMED ONLY)
ENABLED - ACTIVE SIREN ONLY (ARMED ONLY)
ENABLED - ACTIVATE KEYPAD SOUNDER ONLY (ARMED ONLY)
ENABLED - ACTIVATE SIREN & KEYPAD SOUNDER (ARMED ONLY)