Spring Clamp Terminal Block - Mitsubishi Electric FX5UC-96MT/D User Manual

Melsec iq-f fx5uc series
Hide thumbs Also See for FX5UC-96MT/D:
Table of Contents

Advertisement

■Tool
For tightening terminals, use a small, commercially-available screwdriver with a straight tip. The recommended
shape is shown in the figure on the right.
■Precautions
When a precision screwdriver with a small grip is used, the specified tightening torque cannot be obtained. Use
the following screwdriver or equivalent product (grip diameter: 25 mm) to obtain the tightening torque specified
above.
<Reference>
Manufacturer
Phoenix Contact GmbH & Co. KG

Spring Clamp Terminal Block

Wire the spring clamp terminal block in accordance with the following specifications.
For information regarding screw terminal blocks for intelligent function modules, refer to User's manual for each intelligent
function module.
Suitable wiring
The wires to connect the spring clamp terminal block are described below.
No. of wire per terminal
One wire
Wire end treatment
Strip the cable about 10 mm from the tip to connect a wire ferrule at the stripped area. Failure to do so may result in electric
shock or short circuit between adjacent terminals because of the conductive part. If the wire strip length is too short, it may
result in the unstable connection to the spring clamp terminal part.
Depending on the thickness of the sheath, it may be difficult to insert into the insulation sleeve, so select the wires by referring
to the specifications in the diagram.
Strand wire/single wire
10 mm
The following table shows wire ferrules and tools you can remove this part compatible with the terminal block. Use of items
that are not listed in the following table may result in wire ferrule getting stuck to the terminals. Before use, carefully confirm
that the wire ferrule can be removed.
<Reference product>
Manufacturer
PHOENIX CONTACT GmbH & Co. KG
Model
SZS 0.42.5
Wire size
Single wire, Strand wire
2
AWG24 to 16 (0.2 to 1.5 mm
)
Model
AI 0.5-10 WH
AI 0.75-10 GY
A 1.0-10
A 1.5-10
Ferrule with insulation sleeve
2
AWG23 to 19 (0.25 to 0.75 mm
)
Ferrule with insulation sleeve
Insulation sleeve
16 to 18 mm
2 to 2.8 mm
Wire size
2
0.5 mm
2
0.75 mm
2
1.0 mm
2
1.5 mm
With straight tip
2.5 mm
0.4 mm
Ferrules without insulation sleeve
2
AWG23 to 16 (0.25 to 1.5 mm
)
Contact area
(Crimp area)
10 mm
Crimp tool
CRIMPFOX 6
6 WIRING
6.2 Cable Connecting Procedure
6