Capacity of 5 V DC
Current consumption
power supply
Total of current
CPU module
consumed by extension
module
-
720 mA
Capacity of 24 V
Current consumption
DC power supply
Total of current
CPU module
consumed by extension
module
-
500 mA
Result check
Because calculation results for 5 V DC or 24 V DC current consumption are negative, reconfiguration is necessary.
The judgment procedure after reconfiguration is explained on the following pages.

System reconfiguration example

If current consumption of the 5 V DC or 24 V DC power supply is insufficient with the CPU module only, use an extension
power supply module.
Reconfigure the example system configuration using an extension power supply module.
Calculation result
=
1150 mA
-430 mA
Calculation result
=
360 mA
140 mA
The number of transmission points
setting for AnyWireASLINK
Remote
Remote
I/O station
I/O station
4.5 Rules of System Configuration and Examples of Reconfiguration
NG
OK
64 points
Remote
I/O station
To CC-Link
CC-Link
master
station
4 SYSTEM CONFIGURATION
4
69