6.6
Output Wiring
The output wiring of the CPU modules, I/O modules, and terminal modules is explained below.
Transistor output
For output specifications of the CPU modules, refer to Page 34 Output Specifications.
For output specifications of the I/O modules, refer to Page 162 Output specifications.
For output specifications of the terminal modules, refer to Page 180 Output specifications.
Sink and source output
Sink output and source output products are available for transistor outputs of the CPU module, I/O modules, and terminal
modules.
■Differences in circuit
•
Sink output [-common]
Output to make load current flow into the output (Y) terminal is called
sink output.
Load
Y
*1
COM
Fuse
DC power
supply
*1 The number "0" or "1" is applied in .
Handling of transistor output
■Output terminal
For the CPU module, output module (extension connector type), and input/output module (extension connector type), the
transistor output type is a 8-point common output type.
•
Sink output
The COM (number) terminals that are connected each other inside
the PLC are prepared. For external wiring, connect the COM
(number) terminals outside the PLC to reduce the load per one
COM terminal.
Load
Y0
Y1
Fuse
COM0
DC power
COM0
supply
6 WIRING
108
6.6 Output Wiring
• Source output [+common]
Output to make load current flow out of the output (Y) terminal is
called source output.
Load
Y
Fuse
*1
+V
DC power
supply
• Source output
The +V (number) terminals that are connected each other inside the
PLC are prepared. For external wiring, connect the +V (number)
terminals outside the PLC to reduce the load per one +V terminal.
Load
Y0
Y1
DC power
supply
+V0
Fuse
+V0