Toshiba GRL100-701B Instruction Manual page 444

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

List of Information
INF
Description
Standard Information numbers in monitor direction
System Function
0
End of General Interrogation
Transmission completion of GI items.
0
Time Synchronization
Time Synchronization ACK.
2
Reset FCB
Reset FCB(toggle bit) ACK
3
Reset CU
Reset CU ACK
4
Start/Restart
Relay start/restart
5
Power On
Relay power on.
Status Indications
If it is possible to use auto-recloser, this item is set
16 Auto-recloser active
active, if impossible, inactive.
If protection using telecommunication is available,
17 Teleprotection active
this item is set to active. If not, set to inactive.
If the protection is available, this item is set to
18 Protection active
active. If not, set to inactive.
19 LED reset
Reset of latched LEDs
Block the 103 transmission from a relay to control
20 Monitor direction blocked
system. IECBLK: "Blocked" settimg.
Transmission of testmode situation froma relay to
21 Test mode
control system. IECTST "ON" setting.
When a setting change has done at the local, the
22 Local parameter Setting
event is sent to control system.
23 Characteristic1
Setting group 1 active
24 Characteristic2
Setting group 2 active
25 Characteristic3
Setting group 3 active
26 Characteristic4
Setting group 4 active
27 Auxiliary input1
Binary input 1
28 Auxiliary input2
Binary input 2
29 Auxiliary input3
Binary input 3
30 Auxiliary input4
Binary input 4
Supervision Indications
32 Measurand supervision I
Zero sequence current supervision
33 Measurand supervision V
Zero sequence voltage supervision
35 Phase sequence supervision Negative sequence voltage supevision
36 Trip circuit supervision
Output circuit supervision
37 I>>backup operation
38 VT fuse failure
VT failure
39 Teleprotection disturbed
CF(Communication system Fail) supervision
46 Group warning
Only alarming
47 Group alarm
Trip blocking and alarming
Earth Fault Indications
48 Earth Fault L1
A phase earth fault
49 Earth Fault L2
B phase earth fault
50 Earth Fault L3
C phase earth fault
51 Earth Fault Fwd
Earth fault forward
52 Earth Fault Rev
Earth fault reverse
Contents
GI Type
--
--
--
--
--
GI
GI
GI
--
GI
GI
GI
GI
GI
GI
GI
GI
GI
GI
GI
GI
GI
 443 
IEC103 Configurator Default setting
COT
FUN
ID
Signal No. OFF ON
8
10
255
--
6
8
255
--
5
3
192
--
5
4
192
--
5
5
192
--
Not supported
--
1
1, 9, 11, 12
192
1411
1
1, 9, 12
192
1412
1
1, 9, 12
192
1413
1
1, 11, 12
192
1409
1
9, 11
192
1241
1
9, 11
192
1242
Not supported
1
1, 9, 11, 12
192
1243
1
1, 9, 11, 12
192
1244
1
1, 9, 11, 12
192
1245
1
1, 9, 11, 12
192
1246
No set
No set
No set
No set
1
1, 9
192
1267
1
1, 9
192
1268
1
1, 9
192
1269
Not supported
Not supported
1
1, 9
192
891
1
1, 9
192
226
1
1, 9
192
1258
1
1, 9
192
1252
No set
No set
No set
Not supported
Not supported
6 F 2 S 0 8 5 0
DPI
--
--
--
--
--
--
--
--
--
--
--
--
1
2
1
2
1
2
--
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2