Toshiba GRL100-701B Instruction Manual page 441

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

IEC60870-5-103 Configurator
IEC103 configurator software is included in a same CD as RSM100, and can be installed easily as
follows:
Installation of IEC103 Configurator
Insert the CD-ROM (RSM100) into a CDROM drive to install this software on a PC.
Double click the "Setup.exe" of the folder "\IEC103Conf" under the root directory, and operate it
according to the message.
When installation has been completed, the IEC103 Configurator will be registered in the start
menu.
Starting IEC103 Configurator
Click [Start]→[Programs]→[IEC103 Configurator]→[IECConf] to the IEC103 Configurator
software.
Note: The instruction manual of IEC103 Configurator can be viewed by clicking
[Help]→[Manual] on IEC103 Configurator.
Requirements for IEC60870-5-103 master station
Polling cycle: 150ms or more
Timeout time (time till re-sending the request frame to relay): 100ms or more
IEC60870-5-103: Interoperability
1. Physical Layer
1.1 Electrical interface: EIA RS-485
Number of loads, 32 for one protection equipment
1.2 Optical interface
Glass fibre (option)
ST type connector (option)
1.3 Transmission speed
User setting: 9600 or 19200 bit/s
IEC103 master
Data request
Polling cycle:
Response frame
150ms or more
Data request
Response frame
 440 
6 F 2 S 0 8 5 0
GR relay

Hide quick links: