Element
Range
[SP.SYN]
Master/Slave
[CH. CON]
Normal/Exchange
[T.SFT1]
ON/OFF
[T.SFT2]
ON/OFF
[B.SYN1]
ON/OFF
[B.SYN2]
ON/OFF
[LSSV]
ON/OFF
[GPSBAK]
OFF/ON
[AUTO2B](*6)
OFF/ON
[SRCθ](*5)
Disable / I
[IDSV]
OFF/ALM&BLK/ALM
[RYIDSV]
OFF/ON
(*1) Current values shown in parentheses are in the case of 1A rating. Other current values are in the
case of 5A rating.
(*2) This setting is valid for three-terminal application models of the GRL100.
(*3) In the actual setting, one terminal is set to "Master" and other terminal(s) to "Slave".
(*4) OCCHK, [SRCθ] and HYSθ are enabled by setting the [TERM] to "2TERM".
(*5) [AUTO2B] is enabled by setting the [TERM] to "2TERM" and [SRCθ] to "I".
(*6) This setting is only used when there is a fixed difference between the sending and receiving
transmission delay time. When the delay times are equal, the default setting of 0µs must be
used.
(*7) If the channel delay time of CH1 or CH2 exceeds the TDSV setting, then the alarm "Td1 over"
or "Td2 over" is given respectively.
CT Ratio matching
When the CT ratio is different between the local terminal and the remote terminal(s), the CT
ratio matching can be done as follows:
The differential element settings are respectively set to the setting values so that the primary fault
detecting current is the same value at all terminals. Figure 2.2.14.1 shows an example of CT ratio
matching. The settings for DIFI2, DIFGI, DIFSV and DIFIC should also be set with relation to
the primary current in the same manner of the DIFI1 setting.
Step
Default
Master(*3)
Normal
OFF
OFF
ON
ON
OFF
ON
OFF
I
OFF
ON
Primary sensitivity = 800A
Terminal-A
GRL100
CT ratio : 2000/1A
DIFI1=800A / CT ratio(2000/1A)
= 0.4A
Figure 2.2.14.1 Example of CT Ratio Matching
 36 
Remarks
Sampling synchronization
Telecommunication port exchanger
Channel 1 bit shifting for multiplexer
Channel 2 bit shifting for multiplexer
Channel 1 bit synchronising for
multiplexer
Channel 2 bit synchronising for
multiplexer
Disconnector contacts discrepancy
check
Backup synchronization
Automatic mode change
Sampling timing deviation monitoring
with current
Id monitoring
Relay address monitoring
Terminal-B
GRL100
CT ratio : 4000/1A
DIFI1=800A / CT ratio(4000/1A)
= 0.2A
6 F 2 S 0 8 5 0
Communication Mode
A
B