Toshiba GRL100-701B Instruction Manual page 41

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

B.SYN1: is set to 'ON' when the relay is linked via multiplexer, and set to 'OFF' when direct link
is applied. (for channel 1)
This setting is available for CCITT G703-1.2.1, 1.2.2, 1.2.3, X21 and optical interface
(short distance: 2km class). In the case of optical interface 30km and 80km class, this
setting is neglected.
B.SYN2: same as above. (for channel 2)
Setting of RYID, RYID1 and RYID2
Relay address number RYID must take a different number at each terminal.
If the relay address monitoring switch [RYIDSV] is "OFF", their settings are ignored. The
RYID2 setting is enabled by setting the [TERM] to "3TERM" or "Dual".
Two-terminal application: Set the local relay address number to RYID and the remote relay
Three-terminal application: Set the local relay address number to RYID and the remote relay 1
Note: The remote 1 relay is connected by CH1 and the remote 2 relay connected by CH2
Terminal A
RYID=0
RYID1=1
Terminal A
RYID=0
RYID1=1
RYID2=1
Terminal A
RYID=0
RYID1=1
RYID2=2
Figure 2.2.14.3 Communication Link in Three-terminal Line
address number to RYID1. The RYID1 is equal to the RYID of the
remote relay. See Figure 2.2.14.3.
In "Dual" setting, the RYID2 setting must be the same as the RYID1
setting.
address number to RYID1 and the remote relay 2 address number to
RYID2. The RYID1 is equal to the RYID of the remote 1 relay and
the RYID2 equal to the RYID of the remote 2 relay. See Figure
2.2.14.3.
CH1
CH2
(a) Two-terminal Application
CH1
CH2
(b) Two-terminal Application (Dual)
CH1
CH2
CH2
CH1
Terminal C
(c) Three-terminal Application
 40 
6 F 2 S 0 8 5 0
Terminal B
RYID=1
CH1
RYID1=0
CH2
Communication port
Terminal B
RYID=1
CH1
RYID1=0
RYID2=0
CH2
Terminal B
CH2
RYID=1
RYID1=2
RYID2=0
CH1
RYID=2
RYID1=0
RYID2=1