When [ARC-CCB] is set to "MPAR", the center breaker is also reclosed in the multi-phase
autoreclose mode at the time of the TMPR2 setting.
When [ARC-CCB] is set to "OFF", autoreclose does not start for the center breaker.
The scheme switch [ARC-CCB] used in single-phase autoreclose and single- and three-phase
autoreclose is invalid when multi-phase autoreclose is selected as a reclose mode.
The interlinking check scheme for two-breaker autoreclose is shown in Figure 2.15.2.5. Local
interlink check signals CBDS-A, -B and –C are originated by ORing the busbar and center
breaker conditions.
The scheme switch [ARC-SUC] is used to check the autoreclose succeeds. If all three phase CB
contacts have been closed within TSUC time after ARC shot output, it is judged that the
autoreclose has succeeded (AS). If not, it is judged that the autoreclose has failed (AF), and
becomes the final tripping (FT).
The relay provides the user configurable switch [UARCSW] with three-positions (P1, P2, P3) to
be programmed by using PLC function. Any position can be selected. If this switch is not used
for the PLC setting, it is invalid. The setting example is shown in Appendix S.
2.15.2.3 Setting
The setting elements necessary for the autoreclose and their setting ranges are shown in the table
below.
Element
Range
VT
1 - 20000
VTs1
1 - 20000
TSPR1
0.01 – 10.00s
TTPR1
0.01 – 100.00s
TMPR1
0.01 – 100.00s
TRR
0.01 – 100.00s
TEVLV
0.01 – 10.00s
TRDY1
5 – 300s
SYN1
SY1
5 – 75°
θ
SY1UV
10 – 150V
SY1OV
10 – 150V
OVB
10 – 150V
UVB
10 – 150V
OVL1
10 – 150V
UVL1
10 – 150V
TSYN1
0.01 – 10.00s
TLBD1
0.01 – 1.00s
TDBL1
0.01 – 1.00s
T3PLL
0.01 – 1.00s
TW1
0.1 – 10.0s
TS2
5.0 – 300.0s
TS3
5.0 – 300.0s
TS4
5.0 – 300.0s
Step
Default
1
2000
1
2000
0.01s
0.80s
0.01s
0.60s
0.01s
0.80s
0.01s
2.00s
0.01s
0.30s
1s
60s
30°
1V
83V
1V
51V
1V
51V
1V
13 V
1V
51V
1V
13V
0.01s
1.00s
0.01s
0.05s
0.01s
0.05s
0.01s
0.05s
0.1s
0.2s
0.1s
20.0s
0.1s
20.0s
0.1s
20.0s
 129 
6 F 2 S 0 8 5 0
Remarks
VT ratio for line differential protection
VT ratio for voltage and synchronism check
Dead time for single-phase autoreclose and
multi-phase autoreclose
Dead time for three-phase autoreclose
Dead time for multi-phase autoreclose
Autoreclose reset time
Dead time reset for evolving fault
Reclaim time
Synchronism check
Live bus check
Dead bus check
Live line check
Dead line check
Synchronism check time
Voltage check time
Voltage check time
Line three voltage check time
Reclosing signal output time
Second shot dead time
Third shot dead time
Fourth shot dead time