Toshiba GRL100-701B Instruction Manual page 117

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

[ARC-M]
+
"SPAR", "TPAR", "SPAR & TPAR",
&
"MPAR2", "MPAR3"
1571
CB1_READY
52A
52B
52C
TRIP-A
≥1
TRIP-B
≥1
TRIP-C
≥1
[ARC-EXT]
EXT_TRIP-A
1552
"ON"
1553
EXT_TRIP-B
"ON"
1554
EXT_TRIP-C
FT
≥1
(For Leader CB)
(*)ARC
(For Leader CB)
Autoreclose for multi-phase fault
If [ARC-M] is set to "MPAR2" or "MPAR3", only the faulted phases are tripped and the dead
time counter TMPR is started by any of the tripping signals TRIP-A to C. After the dead time has
elapsed, reclosing command ARC is output, based on the status of the linked circuits check
output signal LINK. The voltage check condition can be configured by the PLC function, if the
voltage check and others are required for the reclosing condition.
In other reclosing modes, three-phase tripping is performed and all of TRIP-A to C are activated.
If [ARC-M] is set to "TPAR" or "SPAR & TPAR", the dead time counter TTPR1 for three-phase
reclosing is started. After the dead time has elapsed, reclosing command ARC is output based on
the status of the voltage and synchronism check elements output signal SYN-OP. (The SYN-OP
ARC1 READY
TRDY1
t
0
&
F/F
5-300s
No-Link & Single-phase trip
≥1
TP
( To Figure
2.10.2.8. )
No-Link & Multi-phase trip
DIFG.FS-TRIP
OSTT
STUB
RETRIP
1574
1578
BU-TRIP
LINK condition for MPAR is not satisfied.
Trip when ARC1 READY not operated.
Multi phase trip in SPAR.
Single-phase trip
Multi-phase trip
[ARC-M]
+
"SPAR & TPAR"
(For Leader CB)
+
Figure 2.15.2.1 Autoreclose Scheme
 116 
Single-phase trip
&
≥1
[ARC-M]
+
1824
"SPAR", "SPAR & TPAR"
"Default =CONSTANT 1"
&
[ARC-M]
+
"MPAR2", "MPAR3"
Multi-phase trip
&
≥1
[ARC-M]
+
"TPAR", "SPAR & TPAR"
1825
&
"Default =SYN-OP"
[ARC-M]
+
"MPAR2", "MPAR3"
LINK
&
[ARC-M]
+
1826
"MPAR2", "MPAR3"
"Default =CONSTANT 1"
[ARC-DIFG]
&
"
"
OFF
ARC_BLOCK
≥1
ARC_BLOCK1
&
[ARC-BU]
"
"
OFF
TEVLV
t
0
&
0.01-10s
TRR
0.01-100s
ARC FAIL
&
[ARC-SUC]
"ON"
6 F 2 S 0 8 5 0
TSPR1
t
0
&
&
≥1
0.01-10s
SPR.L-REQ
MSARC
TTPR1
t
0
&
&
0.01-100s
≥1
TPR.L-REQ
TMPR1
t
0
&
&
0.01-10s
MPR.L-REQ
&
≥1
≥1
t
0
TW1
ARC
(For Leader CB)
0.1 - 10s
ARC(*)
M-TRIPA
(For Leader CB)
0.1s
FT
(For Leader CB)
0.2s

Hide quick links: