Toshiba GRL100-701B Instruction Manual page 281

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

displays the name of the module, the name of the output relay, the name of the terminal block
and the terminal number to which the relay contact is connected.
Note: The autoreclose command is assigned to any of the output relays by the user setting. The
following description is the case for the default setting.
In the default setting, the autoreclose command is set to BO9 and BO10 of the IO2 module.
(BO9 is used in the two-breaker autoreclose.)
• Enter 2 to select the IO#2 module, then the LCD displays the screen shown below.
/ 3
B O
I O #
2
B O 1
I O #
2
B O 2
I O #
2
B O 3
. . .
I O #
2
B O 1
I O #
2
B O 1 1
I O #
B O 1 2
2
I O #
2
F A I L
I O #
2
B O 1 3
Move the cursor by pressing the
output relay with one normally open contact.
• Enter 1 and press the ENTER key.
• Press the END key. Then the LCD displays the screen shown below.
/ 3
B O
K e e p
p r e s s i
P r e s s
C A N C E
• Keep pressing the 1 key to forcibly operate the output relay BO10 and check that the
breaker is closed.
• Release pressing the 1 key to reset the operation.
• In case of two-breaker autoreclose, repeat the forcible operation for BO9.
( 0 = D i s a b l e
0
key and select BO10. BO10 is an autoreclose command
n g
1
t o
o p e r a t e .
t o
c a n c e l .
L
 280 
1 = E n a b l e )
1 / 1 4
0
0
0
1
0
0
0
0
6 F 2 S 0 8 5 0