Crimping Guidelines - Fortinet FortiGate-7060E System Manual

8u 19-inch rackmount 6-slot chassis with a 80gbps fabric and 1gbps base backplane
Hide thumbs Also See for FortiGate-7060E:
Table of Contents

Advertisement

DC Power Supply Units (PSUs) and supplying DC power to the chassis
DC PSU (power connector cover removed)
+ (Red)
Power
Connector
- (Black)
Power
Connector
PSU LED States
State
Description
Off
DC power not connected.
Flashing
The PSU is in standby mode, not supplying power to the chassis.
Green
Green
Normal Operation with DC power connected.
Input voltage outside of normal operating range, PSU fan not operating, or output voltage outside of
Amber
normal operating range.
Flashing
Warning that power input or output is close to outside of normal operating range. PSU should be
Amber
replaced.

Crimping guidelines

To connect the PSUs to data center power you should use 8 AWG or larger wires depending on the wire length
and the power requirements of your chassis. The ends of these wires must be fitted with UL approved ring
terminals for 8/M4 studs with ext ring diameter < 9.8 mm. Use the following information to crimp and prepare
these wires.
Do not crimp energized wires.
Follow these crimping guidelines:
Strip the insulation from cable. Be careful not to nick cable strands which may later result in stands breaking.
l
Cable end should be clean: wire brush or clean with emery cloth if necessary. Insert cable into connector until it
l
stops. The insertion length must approximate the stripped length of cable.
15
LED
Latch
FortiGate-7060E Chassis
FortiGate-7060E System Guide