VISTA-128BPT/VISTA-250BPT Installation and Setup Guide
Following is a list of commands used while in the Menu Mode:
#93
Enters Menu Mode.
Serves as [ENTER] key. Press to have keypad accept entry.
[∗]
Backs up to previous screen.
[#]
0
Press to answer NO.
Press to answer YES.
1
Quits Menu Mode and goes back to Data Field Programming Mode, if entered at first prompt of each main menu option.
00, or 000+[∗]

Zone Number Designations

The VISTA-128BPT supports up to 128 zones, the
VISTA-250BPT supports up to 250 zones, of hardwire,
polling loop and/or wireless protection, distributed
among up to eight partitions. The following table lists
the zone numbers and the types of sensors that can be
used with each, and some alternate functions of the
zones.
Zone
Function
1
2-wire Smoke Detectors (if used)
5
Audio Alarm Verification (if used)
7
Keyswitch (if used)
1-9
Traditional Hardwired Zones
9
For unsupervised, N.C. use only.
1-250
5800 Series Wireless Devices
10-250
Polling Loop Devices
∗ + 1 Panic
995
996
# + 3 Panic
∗ + # Panic
999
Zone Defaults
Zone #
Zone Type
001
09
002
03
003
03
004**
04
005
03
006
03
007
03
008
03
009
03
010–250
00
NOTES:
* Zone 992 is the Duress zone. Programming of the zone
response type is not applicable. This zone requires only the
report code programming.
** Zone 004 is also defaulted with Auto-STAY enabled.
4-4
#93 Menu Mode Programming Commands
Zone #
Zone Type
601-632
00
800-830
00
970
00
988
00
990
00
992*
N/A
995
00
996
00
997
05
999
06
Zone Index
The zones are designated as follows:
ZONE #
ZONE
RANGE
FUNCTION
001 – 250
Protection
zones
601 – 632
Relay
Supervisory
Zones
ECP Device
800 – 830
Supervisory
Zones
970, 988,
System
990, & 997
Supervisory
Zones
992, 995 –
Duress and
999
Keypad
Panics
Program supervisory zones with response type of 05.
Communication Defaults
∗45
PRIMARY FORMAT
∗47
SECONDARY FORMAT
∗51
DUAL REPORTING
ACTUAL ZONE
As indicated
6 + 2-digit Relay Number; e.g.,
Relay Number 03 is zone 603.
8 + 2-digit Device Address; e.g.,
Device Address 01 is zone 801.
970:
Bell Supervision
nd
988:
2
Wireless Receiver –
not receiving signals
st
990:
1
Wireless Receiver –
not receiving signals
997:
Polling Loop (short
circuit)
992:
Duress
1 + ∗ panic (A key)
995:
996:
3 + # panic (C key)
∗ + # panic (B key)
999:
[1]
ADEMCO Contact ID
[1]
ADEMCO Contact ID
[0]
no