SETTING THE EXERCISE TIMER

The home generator is equipped with an
exercise timer that will start and exercise the
system once every seven days. During this
exercise period, the unit runs for approximately
20 minutes and then shuts down. Electrical load
transfer DOES NOT occur during the exercise
cycle (unless an utility power outage occurs).
A button on the control panel is labeled "Set
Exercise" (see System Control Panel). The
specific day and the specific time of day this
button is pressed is programmed into the control
board memory. This date and time is then used
to automatically initiate the system exercise
cycle. The "Set Exercise" legend on the control
panel will flash until the set exercise cycle is set.
To perform the Set Exercise procedure:
1. Choose the day and time you want your home
generator to exercise.
2. On that day and time, press and hold down the
"Set Exercise" button for three seconds.
NOTE: "SET EXERCISE" will flash until the
button is pressed for three seconds, then "SET
EXERCISE" will illuminate for 5 seconds, and
finally turn off.
3. The unit will then start and run it's 20 minute
exercise cycle.
For example, if you press the "Set Exercise"
button on Sunday morning at 10:00 AM, the unit
will run an immediate exercise cycle and an
exercise cycle will occur every following Sunday
at 10:100 AM (+/- 1/2 hour).
NOTE: "Set Exercise" will only work if the unit is
in the Automatic mode and this exact procedure
is followed. The exerciser will need to be re-set
whenever the 15 Amp fuse is removed or
changed, or if the 12 Volt DC battery is
disconnected.
If you want to change the day and time the unit
exercises, simply perform the "Set Exercise"
procedure at the exact weekday and time you
want it to take place.

GENERATOR MAINTENANCE

Generator maintenance consists of keeping the
unit clean. Operate the unit in an environment
where it will not be exposed to excessive dust,
dirt, moisture or any corrosive vapors. Cooling air
louvers on the enclosure must not become
clogged with snow, leaves, or any other foreign
material.
Check the cleanliness of the unit frequently and
clean when dust, dirt, oil, moisture or other
foreign substances are visible on its exterior/
interior surface.
NOTE: DO NOT use direct spray from a garden
hose to clean generator. Water can enter the
engine and generator and cause problems.

Engine Maintenance

An engine manual was packaged with this
system. Please refer to it for all engine-related
maintenance topics. However, proper engine
cooling and lubrication are so important we also
reference them.
Engine Oil
The system is filled with the recommended non-
synthetic oil (API SL 10W-30W). This allows for
proper system operation in a wide range of
temperature and climate conditions.
NOTE: Refer to the engine operator's manual for
the recommended oil change intervals.
Shown here is the oil drain location (B) and the
oil filter (A).
Figure2