System Control Panel; Before Initial Engine Start-Up; Engine Oil; Battery Connection - Briggs & Stratton 40213 Installation And Start-Up Manual

15000 rated watts home generator system
Table of Contents

Advertisement

Available languages

Available languages

System Control Panel

Figure 11 depicts the Home Generator System control
panel, located inside the generator housing. Brief
descriptions of the controls used during installation. More
information may be found in the Operator's Manual.
Figure 11 — Home Generator System Control Panel
15 Amp Fuse
System Switch
Set Exercise
Switch
System Switch
This two-position switch is the most important control on
the system and is used as follows:
• "AUTO" position is the normal operating position. If a
utility power outage is sensed, the system will start the
generator.When utility power is restored, lets the engine
stabilize internal temperatures, shuts off the generator,
and waits for the next utility power outage.
• "OFF" position turns off running generator, prevents
unit from starting and resets any detected faults.
15 Amp Fuse
Protects the Home Generator System DC control circuits.
If the fuse has 'blown' (melted open) or was removed, the
engine cannot crank or start. Replace the fuse using only an
identical ATO 15A fuse. One spare fuse is supplied with the
unit.
BEFORE INITIAL START -UP

Engine Oil

This engine is shipped from the factory filled with the
recommended oil. Before starting the engine, check oil level
and ensure that engine is serviced as described in the
engine operator's manual.
Oil Considerations
Your Home Generator System is equipped with an engine
that has been pre-run at the factory and does not require
the traditional "break-in" procedure.
INSTALLATION
Service Tool
Digital Display
Circuit
Breaker
Manual Over-Ride
Switch
CAUTION
Any attempt to crank or start the engine before it has
been properly serviced with the recommended oil will
result in equipment failure.
• Refer to engine manual for oil fill information.
• Damage to equipment resulting from failure to follow this
instruction will void warranty.
The system is filled with synthetic oil (API SJ/CF 5W-
30W).This allows for system operation in the widest range
of temperature and climate conditions.
NOTE: The use of synthetic oil DOES NOT alter the
required oil change intervals described in the engine
operator's manual.

Battery Connection

The Home Generator System is supplied with a 12 Volt DC,
AGM type, 55 Amp-Hour, valve regulated battery. It is a
sealed, lead-acid rechargeable battery. It is installed in the
unit and the battery cables are connected at the factory.The
unit's 15 Amp fuse, which isolates the battery and prevents
the unit from starting, has been removed for shipping.The
battery will lose some charge charge prior to installation of
the generator. If battery voltage is below 12 Volts, charge the
battery.
IMPORTANT: If battery voltage is below 5 Volts, it may
not take a charge and you will need a new battery.
Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1.
Set generator's system switch to OFF.
2.
Remove 15 Amp fuse from control panel.
3.
Disconnect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (-).
CAUTION
Failure to disconnect negative battery cable will result
in equipment failure.
• DO NOT attempt to jump start the battery.
• Damage to equipment resulting from failure to follow this
instruction will void warranty.
4.
Charge battery with battery charger at 2 Amps until
battery holds 12 Volts.
NOTE: DO NOT exceed 13.7 Volts charging.
12

Advertisement

Table of Contents
loading

This manual is also suitable for:

040234

Table of Contents