4.3.1.2

Assigning parameters to the STO

● You can adapt the STO function according to your requirements in the following screen.
● Set the following in the above screen:
● Close the screen.
4.3.1.3

Activate settings

● Click "Copy parameters" and then click "Activate settings":
● If the password = 0 (factory setting), follow the prompts in order to set a password.
● Confirm the prompt for saving your settings (copy RAM to ROM).
● Switch off the Control Unit power supply for approximately 10 seconds (Power ON
Safety Integrated Function Manual, SINAMICS G120
Function Manual, 07/2010, FW 4.3.2, A5E03052391B AA
– ① ② F-DI input filter (debounce time) and monitoring for simultaneous operation
(discrepancy):
The method of functioning of the two filters is described in the section entitled F-DI
signal filtering (Page 57).
– ③ ④ Time interval for forced dormant error detection:
Information regarding forced dormant error detection can be found in the Forced
dormant error detection (Page 40) section.
If you try to set a password that is not permissible, the old password will not be changed.
Further information can be found in the section Password (Page 40).
Reset). Only then will your changes become effective.
Commissioning
4.3 Basic Safety
73