Endress+Hauser Proline Promag 53 Safety Instructions

Hart, profibus dp/pa, foundation fieldbus, modbus rs485 nepsi zone 1, zone 21
Hide thumbs Also See for Proline Promag 53:

Advertisement

Quick Links

Safety Instructions
HART, PROFIBUS DP/PA, FOUNDATION Fieldbus, Modbus RS485
NEPSI Zone 1, Zone 21
Ex documentation
This document is an integral part of the following Operating Instructions:
• BA00047D, Proline Promag 53 HART
• BA00051D, Proline Promag 53 FOUNDATION Fieldbus
• BA00053D, Proline Promag 53 PROFIBBUS DP/PA
• BA00117D, Proline Promag 53 Modbus RS485
Contents
General warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Special conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
COC certificates of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Description of measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Nameplates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Type code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Temperature table compact version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Temperature table remote version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Gas and dust explosion protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Design of measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cable entries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Connection of remote version connecting cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Terminal assignment and connection data, power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Service adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Device fuse. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
XA00126D/06/EN/13.12
71195714

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Proline Promag 53

  • Page 1: Table Of Contents

    Ex documentation This document is an integral part of the following Operating Instructions: • BA00047D, Proline Promag 53 HART • BA00051D, Proline Promag 53 FOUNDATION Fieldbus • BA00053D, Proline Promag 53 PROFIBBUS DP/PA • BA00117D, Proline Promag 53 Modbus RS485 Contents General warnings .
  • Page 2: General Warnings

    IP67, they shall be used. Alternatively Ex e cable glands specified or provided by Endress+Hauser Flowtec AG can be used. The cables must be installed in such a way, that they are fixed in place in order to ensure adequate strain relief.
  • Page 3: Coc Certificates Of Conformity

    Proline Promag 53 NEPSI Zone 1, Zone 21 Installation instructions • Turning the local display: (continued) the screw cap has to be removed before the local display can be turned, and this must be done with the device de-energized (and after a delay of at least 10 minutes following shutdown of the power supply) or when the area is known to be non-hazardous.
  • Page 4: Nameplates

    NEPSI Zone 1, Zone 21 Proline Promag 53 Nameplates The nameplates, which are mounted in a clearly visible position on the transmitter and sensor, contain all of the relevant information about the measuring system. Switzerland 4153 Reinach Promag 5X XXXXX-XXXXXXXXXXXX...
  • Page 5: Type Code

    Proline Promag 53 NEPSI Zone 1, Zone 21 Type code The type code describes the exact design and the equipment of the measuring system. It can be read on the nameplate of the transmitter and sensor and is structured as follows: O M A –...
  • Page 6: Temperature Table Compact Version

    NEPSI Zone 1, Zone 21 Proline Promag 53 Type (compact/remote; Item No. 13 in type code) Type Min. ambient temperature T a min A, P, U –20 °C Compact V, 6 –40 °C G, N, T, W –20 °C Remote 7, 8 –40 °C...
  • Page 7: Temperature Table Remote Version

    Proline Promag 53 NEPSI Zone 1, Zone 21 Temperature table remote Sensor version Max. medium temperature [°C] for T1 T6 in relation to the maximum ambient temperature T (85 °C) (100 °C) (135 °C) (200 °C) (300 °C) (450 °C) 25 to 1200 +50 °C...
  • Page 8: Gas And Dust Explosion Protection

    NEPSI Zone 1, Zone 21 Proline Promag 53 Gas and dust explosion Determine the temperature class for gas in relation to the ambient T and medium temperature T protection Determine the maximum surface temperature for dust in relation to the max. ambient temperature T max.
  • Page 9: Cable Entries

    Proline Promag 53 NEPSI Zone 1, Zone 21 • m for connection compartment (Ex d version): power supply cable and cable of the communication circuit Cable entries  Choice of thread for cable entries M20 × 1.5, ½" NPT or G ½".
  • Page 10: Connection Of Remote Version Connecting Cable

    Ex i (signal circuit) and Ex e (coil circuit). When using the connecting cable supplied by Endress+Hauser, the intrinsic safety of the circuit is ensured at a maximum cable length of 90 m (for IIC) and 200 m (for IIB).
  • Page 11: Electrical Connection

    Proline Promag 53 NEPSI Zone 1, Zone 21 Electrical connection Connection compartment Transmitter housing compact/remote version (terminal assignment, connection data  Page 11 ff.) 4 to 20 mA HART PROFIBUS PA Ex ia * FOUNDATION Fieldbus * – – –...
  • Page 12: Terminal Assignment And Connection Data For Signal Circuits (Intrinsically Safe Circuits)

    NEPSI Zone 1, Zone 21 Proline Promag 53 Terminal assignment and Note! connection data for signal The following tables contain values/specifications, which are dependent on the type code (type of measuring circuits (intrinsically safe device). Please compare the following type code to the one shown on the nameplate of your measuring device.
  • Page 13 Proline Promag 53 NEPSI Zone 1, Zone 21 Terminal assignment of transmitter 53***-***********S Terminal no. (inputs/outputs) Transmitter 20 (+) 21 (–) 22 (+) 23 (–) 24 (+) 25 (–) 26 (+) 27 (–) Pulse/frequency output, Current output HART, Assignment –...
  • Page 14: Terminal Assignment And Connection Data For Signal Circuits (Non-Intrinsically Safe Circuits)

    NEPSI Zone 1, Zone 21 Proline Promag 53 Terminal assignment and Note! connection data for signal The following tables contain values/specifications, which are dependent on the type code (type of measuring circuits (non-intrinsically device). Please compare the following type code to the one shown on the nameplate of your measuring device.
  • Page 15 Proline Promag 53 NEPSI Zone 1, Zone 21 Safety-related and functional values of signal circuits Signal circuits Functional values Safety-related values Current output HART galvanically isolated, intrinsically safe = no active/passive can be selected: = 260 V • active: 0/4 to 20 mA = 500 mA <...
  • Page 16: Service Adapter

    NEPSI Zone 1, Zone 21 Proline Promag 53 Service adapter The service adapter is only used for connecting service interfaces approved by Endress+Hauser. Warning! It is not permissible to connect the service adapter whilst the atmosphere is considered to be explosive.
  • Page 17 Proline Promag 53 NEPSI Zone 1, Zone 21 Endress+Hauser...
  • Page 18 NEPSI Zone 1, Zone 21 Proline Promag 53 Endress+Hauser...
  • Page 19 Proline Promag 53 NEPSI Zone 1, Zone 21 Endress+Hauser...
  • Page 20 www.endress.com/worldwide XA00126D/06/EN/13.12 71195714 FM+SGML 10.0...