6-2 Specifications of Control Terminal

Wire Gauge: 26~16AWG (0.1281-1.318mm
Torque:
5kg-cm [4.3Ib-in.] (0.49 Nm) (As shown in figure above)
8kg-cm [6.94 Ib-in.] (0.78 Nm) (As shown in figure above)
2kg-cm [1.73 lb-in.] (0.19 Nm) (As shown in figure above)
Wiring precautions:
Reserves 5mm and properly install the wire into the terminal; fasten the installation by a
slotted screwdriver. If the wire is stripped, sort the wire before install into the terminal.
Flathead screwdriver: blade width 3.5mm, tip thickness 0.6mm
In the figure above, the factory setting for STO1, STO2, +24V and SCM1, SCM2, DCM are
short circuit. The factory setting for +24V-COM is short circuit and SINK mode (NPN); please
refer to Chapter 4 Wiring for more detail.
Terminals
Digital control signal common
+24V
(Source)
COM
Digital control signal common (Sink)
FWD
Forward-Stop command
REV
Reverse-Stop command
MI1
~
Multi-function input 1~8
MI8
MCM
Multi-function Output Common
Multi-function relay output 1 (N.O.) a Resistive Load:
RA1
Multi-function relay output 1 (N.C.) b
RB1
Multi-function relay common
RC1
Multi-function relay output 2 (N.O.) a
RA2
Multi-function relay output 2 (N.C.) b
RB2
Terminal Function
Chapter 6 Control Terminals|CFP2000 Series
2
);
Factory Setting (NPN mode)
+24V±5% 200mA
Common for multi-function input terminals
FWD-DCM:
ON
forward running
OFF
deceleration to stop
REV-DCM:
ON
reverse running
OFF
deceleration to stop
Refer to parameters 02-01~02-08 to program the
multi-function inputs MI1~MI8.
Source mode
ON: the activation current is 3.3
OFF: cut-off voltage ≦
Sink Mode
ON: the activation current is 3.3mA ≦ 13Vdc
OFF: cut-off voltage ≧ 19Vdc
Max 48Vdc 50mA
3A(N.O.)/3A(N.C.) 250VAC
5A(N.O.)/3A(N.C.) 30VDC
Inductive Load (COS 0.4):
1.2A(N.O.)/1.2A(N.C.) 250VAC
It is used to output each monitor signal, such as drive is in
6-3
mA 11Vdc
5Vdc