Using the Functions

3-5-2 Output Hold Function

1, 2, 3...
For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F = Unit
numbers 10 to 15).
This setting is not valid for the C200H-DA004 (current output model). The output
signal range for the C200-DA004 is 4 to 20 mA, regardless of the settings.
Note After making the DM settings from a Peripheral Device, it will be necessary to
either power up the PC again or turn ON the Special I/O Unit Restart Bit in order
to transfer the contents of the DM settings to the Special I/O Unit. For details re-
garding the Special I/O Unit Restart Bit, refer to 3-7-4 Restarting Special I/O
Units.
The Analog Output Units stop conversion under the following circumstances,
and output the value set by the output hold function.
1. When the Conversion Enable Bit is OFF. (Refer to 3-4-1 IR Area Allocation.)
2. In adjustment mode, when something other than the output number is out-
put during adjustment. (Refer to 3-6-1 Adjustment Mode Operational Flow.)
3. When there is an output setting error. (Refer to 3-5-5 Output Setting Errors.)
4. When a fatal error occurs at the PC. (Refer to the C200HX/HG/HE Program-
ming Manual.)
CLR, HOLD, or MAX can be selected for the output status when conversion is
stopped.
Output signal
range
0 to 10 V
–0.5 V (Min.–5%
of full scale)
–10 to 10 V
0.0 V
1 to 5 V
0.8 V (Min.–5% of
full scale)
4 to 20 mA
3.2 mA (Min.–5%
of full scale)
In order to specify the the output hold function, set from a Peripheral Device the
DM words shown in the following table.
DM word
DM (m+2)
Output 1: Output status when stopped
DM (m+3)
Output 2: Output status when stopped
DM (m+4)
Output 3: Output status when stopped
DM (m+5)
Output 4: Output status when stopped
DM (m+6)
Output 5: Output status when stopped
DM (m+7)
Output 6: Output status when stopped
DM (m+8)
Output 7: Output status when stopped
DM (m+9)
Output 8: Output status when stopped
For the DM word addresses, m = 1000 + 100 x unit number (Units #A to #F = Unit
numbers 10 to 15).
Note After making the DM settings from a Peripheral Device, it will be necessary to
either power up the PC again or turn ON the Special I/O Unit Restart Bit in order
to transfer the contents of the DM settings to the Special I/O Unit. For details re-
garding the Special I/O Unit Restart Bit, refer to 3-7-4 Restarting Special I/O
Units.
CLR
HOLD
Voltage that was output
just prior to stop.
Voltage that was output
just prior to stop.
Voltage that was output
just prior to stop.
Current that was output
just prior to stop.
Function
Section
3-5
MAX
10.5 V (Max.+5%
of full scale)
11.0 V (Max.+5%
of full scale)
5.2 V (Max.+5% of
full scale)
20.8 mA
(Max.+5% of full
scale)
Set value
xx00: CLR
0 output
0
t
t
xx01: HOLD
01 HOLD
Hold output value
Hold output value
prior to stop
p
p
xx02: MAX
O
Output maximum
i
value of range
value of range
Set any value in the
Set any value in the
leftmost bytes (xx).
51