Setting Data - Mitsubishi Melsec-A AJ65SBT User Manual

Cc-link - cc-link/lt bridge module
Table of Contents

Advertisement

3 SPECIFICATIONS
3.7.9 Setting data (2 occupied stations: Address RWrn+4, common to 4 and 8 occupied
stations (4 occupied stations
3 - 25
2 modules): Address RWrn 7)
The setting statuses of the switches for occupied station number setting, transmission
speed setting, point mode setting, test mode and data link last station number are
stored.
• When 2 stations are occupied, the setting data of CC-Link/LT are stored into
RWrn+4.
• When 4 or 8 stations (4 occupied stations
data of CC-Link/LT are stored into RWrn 7.
Bit
Name
Number of occupied
b0 to b1
stations
Transmission speed
b2 to b3
setting
b4 to b5
Point mode setting
b6
Test mode
b7
Not used
Data link last station
b8 to b13
number
b14 to b15 Not used
0: Switch OFF
1: Switch ON
POINT
• The values of this remote register change depending on the occupied station
number setting, point mode setting and last station number setting.
• If any CC-Link/LT remote station connected has a station number setting greater
than the value of the data link last station number, an error of station outside
control range occurs.
2 modules) are occupied, the setting
Description
Setting statuses of the CC-Link side switches SW1, SW2
for operation setting
00: 2 occupied stations
10: 8 occupied stations (4 occupied stations
11: Setting prohibited
Setting statuses of the CC-Link side switches SW8, SW9,
SW10 for operation setting
00: 156kbps
10: 2.5Mbps
Setting statuses of the CC-Link side switches SW4, SW5
for operation setting
00: 8-point mode
10: 16-point mode
Setting status of the CC-Link side switch SW3 for operation
setting
0: Under usual conditions
1: At self-loopback test execution time
The last station number of the remote station that can
perform a data link is stored.
MELSEC-A
01: 4 occupied stations,
2 modules)
01: 625kbps
11: Setting prohibited
01: 4-point mode,
11: Setting prohibited
3 - 25

Advertisement

Table of Contents
loading

Table of Contents