Link Direct Devices

The link direct device allows direct access to the link device of the CC-Link IE Field Network master/local module.
Regardless of the link refresh of the CPU module, the direct reading/writing from/to the link device of the CC-Link IE
Field Network master/local module can be done by using a program.
(1) Specification method
Specify by the following network number and device No.
Specification method: J
(2) Application example
"J2\W10" is for the network No.2 and the link register 10 (W10).
For the bit device (X, Y, B, SB), specify by the digit.
Ex.
J1\K1X0, J10\K4B0
\
Device No.
Link input (RX)
Link output (RY)
Link register (RWw)
Link register (RWr)
Link special relay (SB)
Link special register (SW)
Network number
1 to 239
CC-Link IE Field
Network master/local
MOVP
K100 J2\W10
module of network
number 2
LW 0
LW10
CHAPTER 5 DEVICES
X0 to 3FFF
Y0 to 3FFF
W0 to 1FFF
W2000 to 3FFF
SB0 to 1FF
SW0 to 1FF
5
317